750-463 - 4-channel analog input; For Pt1000/RTD resistance sensors; Adjustable
- Brand: Wago
- Product Code: 750-463
- Available Quantity: 0
$466.50
Technical data
Number of analog inputs | 4 |
Number of Channels | 4 |
Signal type | Resistance measurement |
Signal type (configurable) | yes |
Sensor connection | 4 x (2-wire) |
Data width | 4 x 16-bit data; 4 x 8-bit control/status (optional) |
Resolution (over entire range) | 0.1 °C |
Measurement error (25 °C) | ≤ 0.5 K in temperature range: −30 … +150 °C |
Temperature coefficient | ≤ 20 ppm/K |
Measuring current (typ.) | ≤ 350 µA |
Measurement repetition rate (standard) | 1.1 |
Measurement repetition rate (2-channel/2-conductor) | 0.63 |
Response time (max.) | 4 |
Sensor types | Pt1000; Configurable: Ni1000, KTY 81 |
Temperature range | −30 … +150 °C |
Configuration options | WAGO-I/O-CHECK CODESYS Library e!COCKPIT |
Supply voltage (system) | 5 VDC; via data contacts |
Current consumption (5 V system supply) | 50 |
Supply voltage (field) | 24 VDC (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission via spring contact) |
Isolation | 500 V system/field |
Number of incoming power jumper contacts | 2 |
Number of outgoing power jumper contacts | 2 |
Connection data
Connection technology: inputs / outputs | 8 x CAGE CLAMP® |
Connection type 1 | Inputs/Outputs |
Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
Physical data
Width | 12 mm / 0.472 inches |
Height | 100 mm / 3.937 inches |
Depth | 67.8 mm / 2.669 inches |
Depth from upper-edge of DIN-rail | 60.6 mm / 2.386 inches |
Mechanical data
Mounting type | DIN-35 rail |
Material data
Color | light gray |
Housing material | Polycarbonate; polyamide 6.6 |
Fire load | 0.954 |
Weight | 49.7 |
Conformity marking | CE |
Environmental requirements
Ambient temperature (operation) | 0 … +55 °C |
Surrounding air temperature (storage) | -25 … +85 °C |
Protection type | IP20 |
Pollution degree (5) | 2 per IEC 61131-2 |
Operating altitude | 0 … 2000 m / 0 … 6562 ft |
Mounting position | horizontal (standing/lying); vertical |
Relative humidity (without condensation) | 95 |
Vibration resistance | per IEC 60068-2-6 |
Shock resistance | 15g per IEC 60068-2-27 |
EMC immunity to interference | per EN 61000-6-1; EN 61000-6-2 |
EMC emission of interference | per EN 61000-6-3 |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
Permissible pollutant concentration H2S at a relative humidity < 75% | 10 |