750-469/000-012 - 2-channel analog input; Thermocouple L; Diagnostics
- Brand: Wago
- Product Code: 750-469/000-012
- Available Quantity: 0
$490.20
Technical data
Number of analog inputs | 2 |
Number of Channels | 2 |
Signal type | Thermocouple |
Sensor connection | 2 x (2-wire) |
Data width | 2 x 16-bit data; 2 x 8-bit control/status (optional) |
Internal resistance | 1000 |
Resolution (over entire range) | 0.1 °C |
Conversion time (typ. ≤) | 320 |
Measurement error (25 °C) | < ±6 K (voltage input < ±2 K; cold junction compensation < ±4 K) |
Temperature coefficient | < ±0.2 K/K |
Sensor types | Thermocouple L |
Temperature range | −100 … +900 °C |
Cold junction compensation | at each pair of terminal blocks |
Supply voltage (system) | 5 VDC; via data contacts |
Current consumption (5 V system supply) | 65 |
Isolation | 500 V system/field |
Connection data
Connection technology: inputs / outputs | 8 x CAGE CLAMP® |
Connection type 1 | Inputs/Outputs |
Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
Physical data
Width | 12 mm / 0.472 inches |
Height | 100 mm / 3.937 inches |
Depth | 69.8 mm / 2.748 inches |
Depth from upper-edge of DIN-rail | 62.6 mm / 2.465 inches |
Mechanical data
Mounting type | DIN-35 rail |
Material data
Color | light gray |
Housing material | Polycarbonate; polyamide 6.6 |
Fire load | 0.987 |
Weight | 52.5 |
Conformity marking | CE |
Environmental requirements
Ambient temperature (operation) | 0 … +55 °C |
Surrounding air temperature (storage) | -25 … +85 °C |
Protection type | IP20 |
Pollution degree (5) | 2 per IEC 61131-2 |
Operating altitude | 0 … 2000 m / 0 … 6562 ft |
Mounting position | horizontal (standing/lying); vertical |
Relative humidity (without condensation) | 95 |
Vibration resistance | 4g per IEC 60068-2-6 |
Shock resistance | 15g per IEC 60068-2-27 |
EMC immunity to interference | per EN 61000-6-2, marine applications |
EMC emission of interference | per EN 61000-6-4, marine applications |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
Permissible pollutant concentration H2S at a relative humidity < 75% | 10 |
Permissible pollutant concentration SO 2 at a relative humidity < 75% | 25 |