750-606 - Power Supply; 24 VDC; Diagnostics; Intrinsically safe
- Brand: Wago
- Product Code: 750-606
- Available Quantity: 0
$929.50
Notes
Note | General information (e.g., installation regulations) on explosion protection is available in the WAGO I/O System 750 manuals! |
Technical data
Input voltage (note) | 24 VDC (−25 % … +30 %) |
Diagnostics | Input voltage failure, fuse triggered |
Fuse | electronic |
Power consumption Pmax. | 29 W |
Data width | 2 bits (input voltage failure, fuse triggered) |
Intrinsic safety Ex i | yes |
Supply voltage (system) | 5 VDC; via data contacts |
Current consumption (5 V system supply) | 7.5 |
Supply voltage (field) | 24 VDC (-25 … +30 %); (Adjacent Ex i modules are supplied with UO = max. 27.3 V); via power jumper contacts (power supply via CAGE CLAMP® connection; transmission via spring contact) |
Power loss Pl | < 5 W |
Number of outgoing power jumper contacts | 2 |
Current carrying capacity (power jumper contacts) | 1 |
Marking | ATEX/IECEx: II 3G Ex ec IIC T4 Gc |
Explosion protection
Ex standard | EN IEC 60079-0, -7, -11 |
Power supply (output) | Uo = 26.8 V (safe voltage per IEC 60079-11, protection level ia); Un = 24 V ± 0.3 V, In = 1 A |
Power supply (input) | Un = 24 VDC (-25 … +30 %); Pmax. = 29 W; Um = 253 V |
Connection data
Connection technology: field supply | 2 x CAGE CLAMP® |
Connection type 1 | Field supply |
Solid conductor | 0.08 … 1.5 mm² / 28 … 14 AWG |
Fine-stranded conductor | 0.08 … 1.5 mm² / 28 … 14 AWG |
Strip length | 5 … 6 mm / 0.2 … 0.24 inches |
Physical data
Width | 48 mm / 1.89 inches |
Height | 100 mm / 3.937 inches |
Depth | 70.9 mm / 2.791 inches |
Depth from upper-edge of DIN-rail | 63.7 mm / 2.508 inches |
Mechanical data
Mounting type | DIN-35 rail |
Material data
Color | light gray |
Housing material | Polycarbonate; polyamide 6.6 |
Fire load | 2.544 |
Weight | 167.5 |
Conformity marking | CE |
Environmental requirements
Ambient temperature (operation) | 0 … +55 °C |
Surrounding air temperature (storage) | -25 … +85 °C |
Protection type | IP20 |
Pollution degree (5) | 2 per IEC 61131-2 |
Operating altitude | 0 … 2000 m / 0 … 6562 ft |
Mounting position | horizontal (standing/lying); vertical |
Relative humidity (without condensation) | 95 |
Vibration resistance | 4g per IEC 60068-2-6 |
Shock resistance | 15g per IEC 60068-2-27 |
EMC immunity to interference | per EN 61000-6-2, marine applications |
EMC emission of interference | per EN 61000-6-3, marine applications |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
Permissible pollutant concentration H2S at a relative humidity < 75% | 10 |
Permissible pollutant concentration SO 2 at a relative humidity < 75% | 25 |