Technical data
Topology | Number of IO-Link ports: 4 |
Sensor connection | 4 x (3-wire) |
Actuator connection | 4 x (3-wire) |
Transmission modes | 4.8 kBaud (COM 1), 38.4 kBaud (COM 2), 230.4 kBaud (COM 3) |
Data width | 4–24 bytes, configurable |
Supply voltage (system) | 5 VDC; via data contacts |
Current consumption (5 V system supply) | 40 |
Supply voltage (field) | 24 VDC (-15 … +20 %); via power jumper contacts (power supply via blade contact; transmission via spring contact) |
Current consumption, field supply (module with no external load) | 50 |
Isolation | 500 V system/field |
Number of incoming power jumper contacts | 2 |
Number of outgoing power jumper contacts | 2 |
Connection data
Connection technology: inputs / outputs | 16 x Push-in CAGE CLAMP® |
Connection type 1 | Inputs/Outputs |
Solid conductor | 0.08 … 1.5 mm² / 28 … 16 AWG |
Fine-stranded conductor | 0.25 … 1.5 mm² / 22 … 16 AWG |
Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
Connection requirement (permissible cable length) | 20 |
Conductor type (1) | f-st |
Conductor type (2) | s |
Conductor type 1 | fine-stranded |
Conductor type 2 | solid |
Physical data
Width | 12 mm / 0.472 inches |
Height | 100 mm / 3.937 inches |
Depth | 69 mm / 2.717 inches |
Depth from upper-edge of DIN-rail | 61.8 mm / 2.433 inches |
Mechanical data
Mounting type | DIN-35 rail |
Material data
Color | light gray |
Housing material | Polycarbonate; polyamide 6.6 |
Fire load | 0.824 |
Weight | 49.6 |
Conformity marking | CE |
Environmental requirements
Ambient temperature (operation) | 0 … +55 °C |
Surrounding air temperature (storage) | -25 … +85 °C |
Protection type | IP20 |
Pollution degree (5) | 2 per IEC 61131-2 |
Operating altitude | 0 … 2000 m / 0 … 6562 ft |
Mounting position | horizontal (standing/lying); vertical |
Relative humidity (without condensation) | 95 |
Vibration resistance | per IEC 60068-2-6 |
Shock resistance | 15g per IEC 60068-2-27 |
EMC immunity to interference | per EN 61000-6-2, EN 61131-2 |
EMC emission of interference | per EN 61000-6-4, EN 61131-2 |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
Permissible pollutant concentration H2S at a relative humidity < 75% | 10 |
Permissible pollutant concentration SO 2 at a relative humidity < 75% | 25 |