750-663/000-003 - Intrinsically safe 4-channel digital input; 24 VDC; PROFIsafe V2.0 iPar
- Brand: Wago
- Product Code: 750-663/000-003
- Available Quantity: 0
$1,579.00
Technical data
Number of digital inputs | 4 |
Number of Channels | 4 |
Signal type | Voltage |
Signal type (voltage) | 24 VDC |
Sensor connection | 4 x (Fail-safe input with test pulse) |
Input characteristic | clock sensitive |
Input characteristic | Type 1 |
Input filter (digital) | 0.5 1 2 3 5 10 20 50 100 200 0 |
Input filter | 0 … 200 ms (parameterizable in steps) |
Input filter: parametrizable (channel by channel) | yes |
Input current per channel for signal (1) typ. | 3 |
Output current per channel | 0.05 |
Short-circuit current | ≤ 25 mA |
Signal frequency (max.) | 50 |
Intrinsic safety Ex i | yes |
Configuration options | PROFIsafe address adjustable via DIP switch or engineering software |
Supply voltage (system) | 5 VDC; via data contacts |
Current consumption (5 V system supply) | 145 |
Supply voltage (field) | 24 VDC; (Ex i power supply: UO = max. 27.3 V); via power jumper contacts (power supply via blade contact; transmission via spring contact) |
Current consumption, field supply (module with no external load) | 20 |
Isolation | 300 VAC system/field |
Indicators | LED (A-D) green/red: Status/Error I1 … I4; LED (E) red: Group error; LED (F-H) green/red: Diagnostics |
Number of incoming power jumper contacts | 2 |
Number of outgoing power jumper contacts | 2 |
Current carrying capacity (power jumper contacts) | 1 |
Marking | ATEX/IECEx: II 3 (1) G Ex ec [ia Ga] IIC T4 Gc; II (1) D [Ex ia Da] IIIC; I (M1) [Ex ia Ma] I |
Functional safety
Achievable risk reduction | SIL 3 per IEC 61508; SIL 3 per IEC 61511; SIL 3 per IEC 62061; Cat. 4, PL e per EN ISO 13849 |
Safety standards | IEC 61508; IEC 62061; EN ISO 13849; IEC 61511 |
Explosion protection
Ex standard | EN IEC 60079-0, -7, -11 |
Safety-relevant data (circuit) | Uo = 27.3 V; Io = 23 mA; Po = 157 mW; linear characteristic curve |
Reactances Ex ia IIC | Lo = 61 mH; Co = 64 nF |
Reactances Ex ia IIB | Lo = 100 mH; Co = 552 nF |
Reactances Ex ia IIA | Lo = 100 mH; Co = 2.28 µF |
Reactances Ex ia I | Lo = 100 mH; Co = 2.95 µF |
Reactances (note) | Reactances without accounting for the concurrence of capacitance (Co) and inductance (Lo) |
Connection data
Connection technology: inputs / outputs | 8 x CAGE CLAMP® |
Connection type 1 | Inputs/Outputs |
Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
Connection requirement (permissible cable length) | 100 |
Physical data
Width | 24 mm / 0.945 inches |
Height | 100 mm / 3.937 inches |
Depth | 67.8 mm / 2.669 inches |
Depth from upper-edge of DIN-rail | 60.6 mm / 2.386 inches |
Mechanical data
Mounting type | DIN-35 rail |
Material data
Color | multicoloured |
Housing material | Polycarbonate; polyamide 6.6 |
Fire load | 1.831 |
Weight | 92 |
Conformity marking | CE |
Environmental requirements
Ambient temperature (operation) | 0 … +55 °C |
Surrounding air temperature (storage) | -25 … +85 °C |
Protection type | IP20 |
Pollution degree (5) | 2 per IEC 61131-2 |
Operating altitude | 0 … 2000 m / 0 … 6562 ft |
Mounting position | horizontal (standing/lying); vertical |
Relative humidity (without condensation) | 95 |
Vibration resistance | 4g per IEC 60068-2-6 |
Shock resistance | 15g per IEC 60068-2-27 |
EMC immunity to interference | per EN 61000-6-2, marine applications |
EMC emission of interference | per EN 61000-6-3, marine applications |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
Permissible pollutant concentration H2S at a relative humidity < 75% | 10 |
Permissible pollutant concentration SO 2 at a relative humidity < 75% | 25 |