Description: The 75x-668/000-004 Module features four differential fail-safe analog inputs (AI1 … AI4) and four current-limited sensor supply outputs (L1 … L4). The sensors can be supplied directly by the module or via external 24 V. The fail-safe analog inputs can be used either in single-channel (up to SIL2/PLd) or dual-channel mode (up to SIL3/PLe). Measurement cycle, filter times, encoder evaluation with discrepancy times and tolerance windows can be adjusted to meet the safety function requirements. Overcurrent, overload and wire break are monitored at the fail-safe analog inputs. Both the monitoring and additional safety-relevant functions can be parameterized via WAGO-I/O-CHECK. This configuration tool can be conveniently integrated into engineering systems supporting TCI (Tool Calling Interface) with CC2 or CC3. When exchanging a module, parameters are automatically downloaded from the controller via PROFIsafe-compatible iPar server. The PROFIsafe address can be set using the DIP switch or via WAGO-I/O-CHECK. The module supports both PROFIsafe V2.4 (PROFIBUS) and V2.6 (PROFINET) protocols. Individual input modules can be arranged in any combination when configuring the fieldbus node. If, for example, the cable length of the 24 V supply is greater than 3 m, a WAGO Filter Module or an appropriate external filter must be used for the 24 V power supply to protect the module against surge and burst (per IEC 61000-6-7 and marine applications). Additional information can be found in the product manual (available in German and English)!
Description: The 75x-668/000-004 Module features four differential fail-safe analog inputs (AI1 … AI4) and four current-limited sensor supply outputs (L1 … L4). The sensors can be supplied directly by the module or via external 24 V. The fail-safe analog inputs can be used either in single-channel (up to SIL2/PLd) or dual-channel mode (up to SIL3/PLe). Measurement cycle, filter times, encoder evaluation with discrepancy times and tolerance windows can be adjusted to meet the safety function requirements. Overcurrent, overload and wire break are monitored at the fail-safe analog inputs. Both the monitoring and additional safety-relevant functions can be parameterized via WAGO-I/O-CHECK. This configuration tool can be conveniently integrated into engineering systems supporting TCI (Tool Calling Interface) with CC2 or CC3. When exchanging a module, parameters are automatically downloaded from the controller via PROFIsafe-compatible iPar server. The PROFIsafe address can be set using the DIP switch or via WAGO-I/O-CHECK. The module supports both PROFIsafe V2.4 (PROFIBUS) and V2.6 (PROFINET) protocols. Individual input modules can be arranged in any combination when configuring the fieldbus node. If, for example, the cable length of the 24 V supply is greater than 3 m, a WAGO Filter Module or an appropriate external filter must be used for the 24 V power supply to protect the module against surge and burst (per IEC 61000-6-7 and marine applications). Additional information can be found in the product manual (available in German and English)!
  • Available Quantity: 0

$1,424.00

Notes

Note

Pluggable connectors and coding fingers (753 Series) are not included.

Technical data

Number of analog inputs

4

Number of Channels

4

Signal type

Current

Signal type (current)

0 … 20 mA; 4 … 20 mA

Sensor supply

Outputs L1 … L4

Sensor connection

4 x (2-wire, 3-wire, 4-wire)

Output current per channel

1.5

Output current (module)

1.5

Signal characteristics

Differential

Resolution [bit]

16

Common-mode voltage (max.)

60

Noise rejection at sampling frequency

38

Load impedance

300 Ω

Measurement error, reference temperature

25

Measurement error, deviation max (upper-range value) ≤±

0.05

Temperature error max. (upper-range value) ≤±

0.006

Configuration options

PROFIsafe address adjustable via DIP switch or engineering software

Supply voltage (system)

5 VDC; via data contacts

Current consumption (5 V system supply)

120

Supply voltage (field)

24 VSELV/PELV DC (-15 … +30 %); via power jumper contacts (power supply via blade contact; transmission via spring contact)

Current consumption, field supply (module with no external load)

40

Isolation

500 V system/field

Indicators

LED (E) red, LED (F-H) red/green: Diagnostics; LED (I-M) red/green: Input/output status

Number of incoming power jumper contacts

2

Number of outgoing power jumper contacts

2

Current carrying capacity (power jumper contacts)

10

Current carrying capacity (module)

40 mA

Functional safety

Achievable safety classes

SIL 3; Category 4, PLe (two-channel); SIL 2; Category 2; PLd (one-channel)

Safety standards

IEC 61508-1 … -7; EN ISO 13849-1; EN 62061

Connection data

Connection technology: inputs / outputs

16 x CAGE CLAMP®

Connection type 1

Inputs/Outputs

Solid conductor

0.08 … 2.5 mm² / 28 … 14 AWG

Fine-stranded conductor

0.08 … 2.5 mm² / 28 … 14 AWG

Strip length

9 … 10 mm / 0.35 … 0.39 inches

Physical data

Width

24 mm / 0.945 inches

Height

100 mm / 3.937 inches

Depth

69 mm / 2.717 inches

Depth from upper-edge of DIN-rail

61.8 mm / 2.433 inches

Mechanical data

Mounting type

DIN-35 rail

Material data

Color

yellow

Housing material

Polycarbonate; polyamide 6.6

Fire load

1.611

Weight

84.2

Conformity marking

CE

Environmental requirements

Ambient temperature (operation)

0 … +55 °C

Surrounding air temperature (storage)

-25 … +85 °C

Protection type

IP20

Pollution degree (5)

2 per IEC 61131-2

Operating altitude

0 … 2000 m / 0 … 6562 ft

Mounting position

horizontal (standing/lying); vertical

Relative humidity (without condensation)

95

Shock resistance

15g per IEC 60068-2-27

EMC immunity to interference

per EN 61000-6-2, marine applications, EN 61000-6-7 (FS)

EMC emission of interference

per EN 61000-6-4, marine applications, EN 61000-6-3

Exposure to pollutants

Per IEC 60068-2-42 and IEC 60068-2-43

Data sheet
  • 753-668/000-004 4FAI 0/4-20 mA Diff PROFIsafe

    Download
Manual
  • System Manual WAGO I/O System 750 / 753

    Download
  • 4 FAI 0/4-20 mA; Diff. PROFIsafe

    Download
Bid Text
  • 753-668/000-004

    Download
  • 753-668/000-004

    Download
Instruction Leaflet
  • Gebrauchs- und Montageanleitung

    Download
SISTEMA library
  • SISTEMA-Bibliothek

    Download
  • VDMA-Bibliothek

    Download
Library
    Configuration and Commissioning Software
    • Safety Editor (SEDI) / 750-66x

      Download
    CAE data
    • EPLAN Data Portal 753-668/000-004

      Download