789-1346 - Relay module; Nominal input voltage: 24 VDC; 2 changeover contacts; Limiting continuous current: 8 A; with manual operation; Red status indicator; Module width: 18 mm; 2,50 mm²
- Brand: Wago
- Product Code: 789-1346
- Available Quantity: 0
$85.16
Technical data
Control circuit
Nominal input voltage UN | DC 24 V |
Input voltage range | ±10 % |
Nominal input current at UN | 17 mA |
Load circuit
Number of changeover contacts | 2 |
Contact material (relay) | AgNi |
Limiting continuous current | 8 A |
Inrush current (resistive) max. | (AC) 16 A / 0.02 s; (AC) 12 A / 4 s |
Switching voltage (max.) | AC 250 V |
Switching power (resistive) max. | AC 2000 VA; DC (see load limit curve) |
Recommended minimum load | 12 V / 10 mA |
Pull-in time (typ.) | 15 |
Drop-out time (typ.) | 8 |
Bounce time (typ.) | 7 |
Mechanical life | 5 x 106 switching operations |
Signaling
Status indicator | Red LED |
Safety and protection
Rated voltage | 250 |
Overvoltage category | II |
Pollution degree | 2 |
Dielectric strength (control/load circuit) (AC, 1 min) | 3.5 kVrms |
Dielectric strength (open contact) (AC, 1 min) | 1 kVrms |
Dielectric strength (load/load circuit) (AC, 1 min) | 1.5 kVrms |
Insulation type (control/load circuit) | Reinforced insulation (safe isolation) |
Insulation type (open contact) | Functional insulation |
Insulation type (load/load circuit) | Basic insulation |
Insulation type (adjacent devices) | Reinforced insulation (safe isolation) |
Protection type | IP20 |
Notes
Note | To protect the relay coils and contacts, inductive loads must be dampened with an effective protection circuit. |
Connection data
Connection technology | CAGE CLAMP® |
Solid conductor | 0.2 … 2.5 mm² / 24 … 14 AWG |
Fine-stranded conductor | 0.2 … 2.5 mm² / 24 … 14 AWG |
Strip length | 9 … 10 mm / 0.35 … 0.39 inch |
Physical data
Width | 17.5 mm / 0.689 inch |
Height | 90 mm / 3.543 inch |
Depth from upper-edge of DIN-rail | 55 mm / 2.165 inch |
Mechanical data
Mounting type | DIN-35 rail |
Material data
Fire load | 2.925 |
Weight | 57.6 |
Environmental requirements
Ambient temperature (operation at UN) | -25 … 50 °C |
Surrounding air temperature (storage) | -40 … +70 °C |
Processing temperature | -25 … +50 °C |
Standards and specifications
Standards/specifications | EN 61010-2-201 |