Quick Links


Place here any module, widget, design or HTML. for example menu, categories

IIDM

103011173 - EX-M. 441-11Y-14-1276-2

Description: Product type description:EX-(1) 441-11Y-(2)-(3)-1276-2(1)M.Snap actionT.Slow action (not for AF/S)(2)UESlow action with overlapping contacts(3)withoutLever selection, refer to catalogue
Description: Product type description:EX-(1) 441-11Y-(2)-(3)-1276-2(1)M.Snap actionT.Slow action (not for AF/S)(2)UESlow action with overlapping contacts(3)withoutLever selection, refer to catalogue
Productfeatures
  • 2 cable entries
  • Suitable for heavy duty
Data
Ordering data

Product type description

EX-M. 441-11Y-14-1276-2

Article number (order number)

103011173

EAN (European Article Number)

4030661476476

eCl@ss number, version 9.0

27-27-06-01

eCl@ss number, version 11.0

27-27-06-01

eCl@ss number, version 12.0

27-27-06-01

ETIM number, version 7.0

EC000030

ETIM number, version 6.0

EC000030

Approvals - Standards

Certificates

INMETRO

DEKRA

DEKRA EX

Explosion protection

Explosion protection: regulations

EN 60079-0

EN 60079-31

Explosion protection zones

21

Explosion protection category

2D

Explosion protection designation

II 2D Ex tb IIIC T90°C Db

General data

Standards

EN 60947-5-1

Working principle

mechanical

Enclosure material

Grey cast iron, galvanised

Enclosure coating material

painted

Material of the contacts, electrical

Silver

Gross weight

1,785 g

General data - Features

Number of openers

1

Number of shutters

1

Mechanical data

Mechanical life, minimum

10,000,000 Operations

Contact opening

2 x 2.5 mm

Mechanical data - Connection technique

Type of connection

Screw terminals M20 x 1.5

Cable section, minimum

1.5 mm²

Cable section, maximum

2.5 mm²

Wire cross-section

13 AWG

Mechanical data - Dimensions

Length of sensor

63 mm

Width of sensor

106 mm

Height of sensor

181 mm

Ambient conditions

Degree of protection

IP65

IP67

IP66

Ambient temperature, minimum

-20 °C

Ambient temperature, maximum

+60 °C

Ambient conditions - Insulation values

Rated insulation voltage U

250 V

Rated impulse withstand voltage U

4 kV

Electrical data

Thermal test current

16 A

Utilisation category AC-15

230 VAC

Utilisation category AC-15

4 A

Switching element

NO contact, NC contact

Switching principle

Snap switch element

Bounce duration, maximum

5 ms

Switching frequency

3,000 /h

Switchover time, maximum

35 ms

Operating instructions and Declaration of conformity
  • EX-T/M 441

    Download
  • TraceParts

    Download