750-1491 - 2-channel analog input; Resistor bridges (strain gauge)
- Brand: Wago
- Product Code: 750-1491
- Available Quantity: 0
$562.50
Technical data
Number of analog inputs | 2 |
Number of Channels | 2 |
Signal type | Resistor bridge (strain gauge) |
Supply voltage (sensor) | 5 VDC |
Signal voltage UD | ±15 mV; ±30 mV; ±60 mV; ±120 mV; ±240 mV; ±360 mV |
Signal voltage Uref | Internal +5 V; External ±5 V; ±10 V; ±15 V |
Resolution [bit] | 16 |
Data width | 4 x 16-bit data; 4 x 8-bit control/status (optional) |
Internal resistance | > 200 kΩ (Uref), > 1.4 MΩ (Ud) |
Conversion time | 10 ms (min.) |
Measurement error (25 °C) | UD: ±30 µV; Uref: ±0.05 % of the upper-range value |
Measurement error over entire temperature range | ±0.2 % of the upper-range value; with user calibration up to ±0.05 % |
Supply voltage (system) | 5 VDC; via data contacts |
Current consumption (5 V system supply) | 70 |
Current consumption (system and sensor) | 200 |
Isolation | Per UL 61010-2-201: 1.2 kVDC system/channel and channel/channel |
Connection data
Connection technology: inputs / outputs | 16 x Push-in CAGE CLAMP® |
Connection type 1 | Inputs/outputs |
Solid conductor | 0.08 … 1.5 mm² / 28 … 16 AWG |
Fine-stranded conductor | 0.25 … 1.5 mm² / 22 … 16 AWG |
Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
Physical data
Width | 12 mm / 0.472 inches |
Height | 100 mm / 3.937 inches |
Depth | 69 mm / 2.717 inches |
Depth from upper-edge of DIN-rail | 61.8 mm / 2.433 inches |
Mechanical data
Mounting type | DIN-35 rail |
Material data
Color | light gray |
Housing material | Polycarbonate; polyamide 6.6 |
Fire load | 0.824 |
Weight | 44.9 |
Conformity marking | CE |
Environmental requirements
Ambient temperature (operation) | 0 … +55 °C |
Surrounding air temperature (storage) | -25 … +85 °C |
Protection type | IP20 |
Pollution degree (5) | 2 per IEC 61131-2 |
Operating altitude | 0 … 2000 m / 0 … 6562 ft |
Mounting position | horizontal (standing/lying); vertical |
Relative humidity (without condensation) | 95 |
Shock resistance | 15g per IEC 60068-2-27 |
EMC immunity to interference | per EN 61000-6-2 |
EMC emission of interference | per EN 61000-6-3 |
Exposure to pollutants | per IEC 60068-2-42 and IEC 60068-2-43 |