Description: The Modbus TCP / UDP Fieldbus Coupler 750-362 connects the digital, analog and specialty modules of the WAGO-I/O-System via ETHERNET. Two ETHERNET interfaces and the integrated switch allow the fieldbus to be wired in line topology. Additional infrastructure elements such as switches or hubs can be eliminated. Both interfaces support Autonegotiation and Auto-MDI(X). The last byte of the IP address and the IP address (DHCP, BootP, fixed) can be specified with the DIP switch. The coupler is suitable for fieldbus communication in MODBUS networks. In addition, a large number of standardized ETHERNET Protocols supported (HTTP (S), BootP, DHCP, DNS, SNMP, (S) FTP). An integrated web server provides configuration options and status information of the coupler.
Description: The Modbus TCP / UDP Fieldbus Coupler 750-362 connects the digital, analog and specialty modules of the WAGO-I/O-System via ETHERNET. Two ETHERNET interfaces and the integrated switch allow the fieldbus to be wired in line topology. Additional infrastructure elements such as switches or hubs can be eliminated. Both interfaces support Autonegotiation and Auto-MDI(X). The last byte of the IP address and the IP address (DHCP, BootP, fixed) can be specified with the DIP switch. The coupler is suitable for fieldbus communication in MODBUS networks. In addition, a large number of standardized ETHERNET Protocols supported (HTTP (S), BootP, DHCP, DNS, SNMP, (S) FTP). An integrated web server provides configuration options and status information of the coupler.
  • Available Quantity: 4

$502.40

Technical data

Communication

Modbus (TCP, UDP)

ETHERNET protocols

HTTP(S)

BootP

DHCP

DNS

SNTP

FTP(S)

SNMP

Baud rate

10/100 Mbit/s

Transmission medium

Twisted Pair S-UTP; 100 Ω; Cat. 5; 100 m maximum cable length

Transmission performance

Class D per EN 50173

Number of modules per node (max.)

250

Number of modules without a bus extension (max.)

64

Input and output process image (fieldbus) max.

1020 Worte/1020 Worte

Supply voltage (system)

24 VDC (-25 … +30 %); via pluggable connector

Current consumption (5 V system supply)

350

Total current (system supply)

700

Input current (typ.) at nominal load (24 V)

280

Power supply efficiency (typ.) at nominal load (24 V)

90

Isolation

500 V system/field

Indicators

LED (LINK/ACT) green: Network connection via ports 1 … 2; LED (MS, NS) red/green: Status of node, network; LED (I/O) red/green/orange: Status of local data bus

Connection data

Connection technology: communication/fieldbus

Modbus TCP/UDP: 2 x RJ-45

Connection technology: system supply

2 x CAGE CLAMP®

Connection technology: device configuration

1 x Male connector; 4-pole

Connection type 1

System supply

Solid conductor

0.08 … 2.5 mm² / 28 … 14 AWG

Fine-stranded conductor

0.08 … 2.5 mm² / 28 … 14 AWG

Strip length

8 … 9 mm / 0.31 … 0.35 inches

Physical data

Width

49.5 mm / 1.949 inches

Height

96.8 mm / 3.811 inches

Depth

71.9 mm / 2.831 inches

Depth from upper-edge of DIN-rail

64.7 mm / 2.547 inches

Mechanical data

Mounting type

DIN-35 rail

Material data

Color

-

Housing material

Polycarbonate; polyamide 6.6

Fire load

1.394

Weight

104.8

Conformity marking

CE

Environmental requirements

Ambient temperature (operation)

0 … +55 °C

Surrounding air temperature (storage)

-25 … +85 °C

Protection type

IP20

Pollution degree (5)

2 per IEC 61131-2

Operating altitude

0 … 2000 m / 0 … 6562 ft

Mounting position

horizontal (standing/lying); vertical

Relative humidity (without condensation)

95

Vibration resistance

4g per IEC 60068-2-6

Shock resistance

15g per IEC 60068-2-27

EMC immunity to interference

per EN 61000-6-2, marine applications

EMC emission of interference

per EN 61000-6-3, marine applications

Exposure to pollutants

Per IEC 60068-2-42 and IEC 60068-2-43

Permissible pollutant concentration H2S at a relative humidity < 75%

10

Permissible pollutant concentration SO 2 at a relative humidity < 75%

25

Manual
  • System Manual WAGO I/O System 750 / 753

    Download
  • Fieldbus Coupler Modbus TCP

    Download
  • System Manual Series 750/753

    Download
Bid Text
  • 750-362

    Download
  • 750-362

    Download
  • ausschreiben.de 750-362

    Download
Additional Information
  • Disposal; Electrical and electronic equipment, Packaging

    Download
System Description
  • 750/753 Series I/O-System ‒ General Product Information

    Download
  • Use in Hazardous Environments

    Download
  • Overview on WAGO-I/O-SYSTEM 750 approvals

    Download
Firmware
  • 0750-036x, Feldbuskoppler

    Download
CAD data
  • 2D/3D Models 750-362

    Download
CAE data
  • ZUKEN Portal 750-362

    Download
  • EPLAN Data Portal 750-362

    Download
Compliance Search
  • Environmental Product Compliance 750-362

    Download