750-404/040-003 - Counter; Adjustable; Extreme
- Brand: Wago
- Product Code: 750-404/040-003
- Available Quantity: 0
$638.00
Technical data
Number of digital outputs | 2 |
Number of counters | 1 |
Signal type | Voltage |
Signal type (voltage) | 24 VDC |
Counter depth | 32 |
Input current (typ.) | 7 mA |
Output current per channel | 0.5 |
Output current | short-circuit-protected |
Switching frequency (max.) | 100 kHz |
Voltage range for signal (0) | −3 … +5 VDC |
Voltage range for signal (1) | 15 … 30 VDC |
Operating mode | Up/down counter/100 kHz; Up counter/enable input; Peak-time counter; Frequency measurement: 0.1 Hz … 100 kHz (Default setting); Up/down counter/signal outputs (DO); Two up counters/16 bits/5 kHz |
Data width | 32-bit data; 8-bit control/status |
Supply voltage (system) | 5 VDC; via data contacts |
Current consumption (5 V system supply) | 70 |
Supply voltage (field) | 24 VDC (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission via spring contact); Derating must be observed! |
Rated surge voltage | 1 kV |
Number of incoming power jumper contacts | 2 |
Number of outgoing power jumper contacts | 2 |
Current carrying capacity (power jumper contacts) | 10 |
Derating | Derating (supply voltage): Ambient temperatures under laboratory conditions: (−25 … +30 %); for −40 … +55 °C: 24 V (−25 … +20 %); for +55 … +70 °C: 24 V (−25 … +10 %); Lower limit in all temperature ranges: −27.5 % (including 15 % residual ripple) |
Connection data
Connection technology: inputs / outputs | 8 x CAGE CLAMP® |
Connection type 1 | Inputs/Outputs |
Solid conductor | 0.25 … 2.5 mm² / 24 … 14 AWG |
Fine-stranded conductor | 0.25 … 2.5 mm² / 24 … 14 AWG |
Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
Physical data
Width | 12 mm / 0.472 inches |
Height | 100 mm / 3.937 inches |
Depth | 67.8 mm / 2.669 inches |
Depth from upper-edge of DIN-rail | 60.6 mm / 2.386 inches |
Mechanical data
Mounting type | DIN-35 rail |
Material data
Color | dark gray |
Housing material | Polycarbonate; polyamide 6.6 |
Fire load | 0.147 |
Weight | 49.3 |
Conformity marking | CE |
Environmental requirements
Ambient temperature (operation) | -40 … +70 °C |
Surrounding air temperature (storage) | -40 … +85 °C |
Protection type | IP20 |
Pollution degree (5) | 2 per IEC 61131-2 |
Operating altitude | without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.) |
Mounting position | horizontal (standing/lying); vertical |
Relative humidity (without condensation) | 95 |
Relative humidity (with condensation) | Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation) |
Vibration resistance | per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3, EN 50155; EN 61373 |
Shock resistance | per IEC 60068-2-27 (15g/11 ms/half-sine/1,000 shocks; 25g/6 ms/1,000 shocks), EN 50155, EN 61373 |
EMC immunity to interference | Per EN 61000-6-1, -2; EN 61131-2; marine applications; EN 50121-3-2; EN 50121-4, -5; EN 60255-26; |
EMC emission of interference | per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3, EN 50121-3-2, EN 50121-4, -5 |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
Permissible pollutant concentration H2S at a relative humidity < 75% | 10 |