Quick Links


Place here any module, widget, design or HTML. for example menu, categories

IIDM

750-484 - 2-channel analog input; 4 … 20 mA HART; Intrinsically safe

  • Brand: Wago
  • Product Code: 750-484
Description: This analog input module connects two field-side signal conditioners equipped with a HART interface that are to be used in hazardous areas of Zone 0+1. The module supplies signal conditioners, reads process values via analog interface, and enables HART communication for configuring and importing dynamic variables. The WAGO I/O System 750 must be installed either in Zone 2 or in a non-hazardous area. The 24 V supply is supplied to the field contacts (HART +) from the power jumper contacts via multipliers. The shield directly connects to the DIN-rail. The measurement input is equipped with current limitation, which limits the current to 25 mA. This module powers 2-wire signal conditioners without dedicated power supply. Up to 4 HART dynamic variables (PV, SV, TV, QV) per channel can be mapped in the cyclic process image of the coupler or controller (parameterizable). For HART communication with connected intelligent HART field devices, the HART protocol can be mapped in the cyclic process image of the coupler or controller (parameterizable). FDT/DTM device drivers are available for select (programmable) couplers, allowing HART tool routing to the connected HART device.
Description: This analog input module connects two field-side signal conditioners equipped with a HART interface that are to be used in hazardous areas of Zone 0+1. The module supplies signal conditioners, reads process values via analog interface, and enables HART communication for configuring and importing dynamic variables. The WAGO I/O System 750 must be installed either in Zone 2 or in a non-hazardous area. The 24 V supply is supplied to the field contacts (HART +) from the power jumper contacts via multipliers. The shield directly connects to the DIN-rail. The measurement input is equipped with current limitation, which limits the current to 25 mA. This module powers 2-wire signal conditioners without dedicated power supply. Up to 4 HART dynamic variables (PV, SV, TV, QV) per channel can be mapped in the cyclic process image of the coupler or controller (parameterizable). For HART communication with connected intelligent HART field devices, the HART protocol can be mapped in the cyclic process image of the coupler or controller (parameterizable). FDT/DTM device drivers are available for select (programmable) couplers, allowing HART tool routing to the connected HART device.
  • Available Quantity: 0

$1,322.00

Notes

Note

The analog output module must only be operated via 24 VDC Ex i!

General information (e.g., installation regulations) on explosion protection is available in the WAGO I/O System 750 manuals!

Technical data

Number of analog inputs

2

Number of Channels

2

Signal type

Current

Signal type (current)

4 … 20 mADC

Supply voltage (sensor)

16.5 VDC; Transmitter supply UV at 20 mA

Sensor connection

2 x (2-wire)

Input filter

parameterizable

Input filter: parametrizable (channel by channel)

yes

Signal characteristics

Single-ended

Diagnostics

Wire break, measurement range overflow

Resolution [bit]

12

Power consumption Pmax.

1.60 W (with slaves (20 mA))

Data width

2 x 2-byte data; 2 x 2-byte data + 2n x 4-byte data (n = number of dynamic variables); 2 x 2-byte data + 6-byte mailbox

Overvoltage protection

30 V, reverse polarity protected

Conversion time (typ. ≤)

10

Measurement error, reference temperature

25

Measurement error, deviation max (upper-range value) ≤±

0.2

Temperature error max. (upper-range value) ≤±

0.01

Intrinsic safety Ex i

yes

Configuration options

WAGO-I/O-CHECK

e!COCKPIT

Supply voltage (system)

5 VDC; via data contacts

Current consumption (5 V system supply)

25

Supply voltage (field)

24 VDC; (Ex i power supply: UO = max. 27.3 V); via power jumper contacts (power supply via blade contact; transmission via spring contact)

Current consumption, field supply (module with no external load)

26

HART devices per channel

1 device (single-drop, no multi-drop)

HART modems per channel

1 modem (no multiplex)

Power loss Pl

0.62 W (without slaves)

Isolation

300 VAC system/field

Number of incoming power jumper contacts

2

Number of outgoing power jumper contacts

2

Current carrying capacity (power jumper contacts)

1

Marking

ATEX/IECEx: II 3 (1) G Ex ec [ia Ga] IIC T4 Gc; II (1) D [Ex ia Da] IIIC; I (M1) [Ex ia Ma] I

Explosion protection

Ex standard

EN IEC 60079-0, -7, -11

Safety-relevant data (circuit)

Uo = 27.3 V; Io = 92.7 mA; Po = 630 mW; Linear characteristic curve

Reactances Ex ia IIC

Lo = 1.5 mH; Co = 87 nF

Reactances Ex ia IIB

Lo = 15 mH; Co = 670 nF

Reactances Ex ia IIA

Lo = 38 mH; Co = 2.2 μF

Reactances Ex ia I

Lo = 36 mH; Co = 3.49 µF

Reactances (note)

Reactances without accounting for the concurrence of capacitance (Co) and inductance (Lo)

Connection data

Connection technology: inputs / outputs

16 x CAGE CLAMP®

Connection type 1

Inputs/Outputs

Solid conductor

0.08 … 2.5 mm² / 28 … 14 AWG

Fine-stranded conductor

0.08 … 2.5 mm² / 28 … 14 AWG

Strip length

8 … 9 mm / 0.31 … 0.35 inches

Physical data

Width

24 mm / 0.945 inches

Height

100 mm / 3.937 inches

Depth

67.8 mm / 2.669 inches

Depth from upper-edge of DIN-rail

60.6 mm / 2.386 inches

Mechanical data

Mounting type

DIN-35 rail

Material data

Color

blue

Housing material

Polycarbonate; polyamide 6.6

Fire load

1.682

Weight

92

Conformity marking

CE

Environmental requirements

Ambient temperature (operation)

0 … +55 °C

Surrounding air temperature (storage)

-25 … +85 °C

Protection type

IP20

Pollution degree (5)

2 per IEC 61131-2

Operating altitude

0 … 2000 m / 0 … 6562 ft

Mounting position

horizontal (standing/lying); vertical

Relative humidity (without condensation)

95

Vibration resistance

4g per IEC 60068-2-6

Shock resistance

15g per IEC 60068-2-27

EMC immunity to interference

per EN 61000-6-2, marine applications

EMC emission of interference

per EN 61000-6-3, marine applications

Exposure to pollutants

Per IEC 60068-2-42 and IEC 60068-2-43

Permissible pollutant concentration H2S at a relative humidity < 75%

10

Permissible pollutant concentration SO 2 at a relative humidity < 75%

25

Data sheet
  • 750-484, 2AI 4-20mA 12 Bit S.E. HART Ex i, data sheet

    Download
Manual
  • System Manual WAGO I/O System 750 / 753

    Download
  • 2-channel, 4-20mA, HART, Ex i, single ended

    Download
Bid Text
  • 750-484

    Download
  • 750-484

    Download
Additional Information
  • Disposal; Electrical and electronic equipment, Packaging

    Download
System Description
  • Overview on WAGO-I/O-SYSTEM 750 approvals

    Download
  • Ex i Overview

    Download
  • Use in Hazardous Environments

    Download
  • 750/753 Series I/O-System ‒ General Product Information

    Download
Application Note CoDeSys 2.3
  • HART Tool Routing via PROFIBUS with 750-833 and 750-333 (a116140)

    Download
  • HART Tool Routing via ETHERNET with
    750-820x/750-88x and CODESYS 2.3 (a116120)

    Download
Application Note e!COCKPIT
  • HART Tool Routing via ETHERNET with 750-820x and e!RUNTIME (a116130)

    Download
Application note, other
  • HART Tool-routing with Emerson AMS (a116110)

    Download
Library
  • Connecting HART-Modules 750-482 and 750-484

    Download
  • Utilize HART-Modules 750-482 and 750-484

    Download
CAE data
  • EPLAN Data Portal 750-484

    Download
  • WSCAD Universe 750-484

    Download
  • ZUKEN Portal 750-484

    Download
CAD data
  • 2D/3D Models 750-484

    Download
Device Driver
  • ModbusTCP/ HART Gateway DTM / HART 750-48x, 753-48x

    Download
  • 759-360; Profibus/ HART Gateway DTM / HART 750-48x , 753-48x

    Download
  • WAGO USB Service Kabel Treiber / Serie 750 und 857

    Download