750-485 - 2-channel analog input; 4 … 20 mA; Single-ended; Intrinsically safe
- Brand: Wago
- Product Code: 750-485
- Available Quantity: 0
$1,139.00
Notes
Note | The analog output module must only be operated via 24 VDC Ex i! General information (e.g., installation regulations) on explosion protection is available in the WAGO I/O System 750 manuals! |
Technical data
Number of analog inputs | 2 |
Number of Channels | 2 |
Signal type | Current |
Signal type (current) | 4 … 20 mADC |
Supply voltage (sensor) | 16 VDC; Transmitter supply UV at 20 mA |
Sensor connection | 2 x (3-wire) |
Signal characteristics | Single-ended |
Resolution [bit] | 12 |
Input resistance (max.) | 100 |
Power consumption Pmax. | 1.3 W |
Data width | 2 x 16-bit data; 2 x 8-bit control/status (optional) |
Conversion time (typ. ≤) | 2 |
Measurement error, reference temperature | 25 |
Measurement error, deviation max (upper-range value) ≤± | 0.2 |
Temperature error max. (upper-range value) ≤± | 0.01 |
Intrinsic safety Ex i | yes |
Supply voltage (system) | 5 VDC; via data contacts |
Current consumption (5 V system supply) | 31 |
Supply voltage (field) | 24 VDC; (Ex i power supply: UO = max. 27.3 V); via power jumper contacts (power supply via blade contact; transmission via spring contact) |
Current consumption, field supply (module with no external load) | 11 |
Power loss Pl | 0.75 W |
Isolation | 300 VAC system/field |
Number of incoming power jumper contacts | 2 |
Number of outgoing power jumper contacts | 2 |
Marking | ATEX/IECEx: II 3 (1) G Ex ec [ia Ga] IIC T4 Gc; II (1) D [Ex ia Da] IIIC; I (M1) [Ex ia Ma] I |
Explosion protection
Ex standard | EN IEC 60079-0, -7, -11 |
Safety-relevant data (circuit) | Uo = 27.3 V; Io = 90 mA; Po = 0.61 W; Linear characteristic curve |
Reactances Ex ia IIC | Lo = 5 mH; Co = 88 nF |
Reactances Ex ia IIB | Lo = 18 mH; Co = 680 nF |
Reactances Ex ia IIA | Lo = 40 mH; Co = 2.2 μF |
Reactances Ex ia I | Lo = 100 mH; Co = 3.5 µF |
Reactances (note) | Reactances without accounting for the concurrence of capacitance (Co) and inductance (Lo) |
Connection data
Connection technology: inputs / outputs | 16 x CAGE CLAMP® |
Connection type 1 | Inputs/Outputs |
Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
Physical data
Width | 24 mm / 0.945 inches |
Height | 100 mm / 3.937 inches |
Depth | 67.8 mm / 2.669 inches |
Depth from upper-edge of DIN-rail | 60.6 mm / 2.386 inches |
Mechanical data
Mounting type | DIN-35 rail |
Material data
Color | blue |
Housing material | Polycarbonate; polyamide 6.6 |
Fire load | 2.027 |
Weight | 97.6 |
Conformity marking | CE |
Environmental requirements
Ambient temperature (operation) | 0 … +55 °C |
Surrounding air temperature (storage) | -25 … +85 °C |
Protection type | IP20 |
Pollution degree (5) | 2 per IEC 61131-2 |
Operating altitude | 0 … 2000 m / 0 … 6562 ft |
Mounting position | horizontal (standing/lying); vertical |
Relative humidity (without condensation) | 95 |
Vibration resistance | 4g per IEC 60068-2-6 |
Shock resistance | 15g per IEC 60068-2-27 |
EMC immunity to interference | per EN 61000-6-2, marine applications |
EMC emission of interference | per EN 61000-6-3, marine applications |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
Permissible pollutant concentration H2S at a relative humidity < 75% | 10 |
Permissible pollutant concentration SO 2 at a relative humidity < 75% | 25 |