750-562 - 2-channel analog output; 0 … 10 V/±10 VDC; 16 bits
- Brand: Wago
- Product Code: 750-562
- Available Quantity: 0
$571.70
Technical data
Number of analog outputs | 2 |
Number of Channels | 2 |
Signal type | Voltage |
Signal type (voltage) | 0 … 10 VDC; -10 … +10 VDC |
Signal type (configurable) | yes |
Actuator connection | 2 x (2-wire, 4-wire) |
Resolution [bit] | 16 |
Data width | 2 x 16-bit data; 2 x 8-bit control/status (optional) |
Load impedance (voltage output) | ≥ 5 kΩ |
Conversion time (typ. ≤) | 5 |
Measurement error, reference temperature | 25 |
Measurement error, deviation max (upper-range value) ≤± | 0.05 |
Output error, deviation (max.) of the upper-range value | 0.05 |
Temperature coefficient | < ±100 ppm |
Recovery time (typ.) | 0.3 |
Configuration options | WAGO-I/O-CHECK e!COCKPIT |
Supply voltage (system) | 5 VDC; via data contacts |
Current consumption (5 V system supply) | 125 |
Supply voltage (field) | 24 VDC (-15 … +20 %); via power jumper contacts (power supply via blade contact; transmission via spring contact) |
Isolation | 500 V system/field |
Number of incoming power jumper contacts | 2 |
Number of outgoing power jumper contacts | 2 |
Connection data
Connection technology: inputs / outputs | 8 x CAGE CLAMP® |
Connection type 1 | Inputs/Outputs |
Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Strip length | 8 … 9 mm / 0.31 … 0.35 inch |
Physical data
Width | 12 mm / 0.472 inch |
Height | 100 mm / 3.937 inch |
Depth | 69.8 mm / 2.748 inch |
Depth from upper-edge of DIN-rail | 62.6 mm / 2.465 inch |
Mechanical data
Mounting type | DIN-35 rail |
Material data
Color | light gray |
Housing material | Polycarbonate; polyamide 6.6 |
Fire load | 0.954 |
Weight | 50.5 |
Conformity marking | CE |
Environmental requirements
Ambient temperature (operation) | 0 … +55 °C |
Surrounding air temperature (storage) | -25 … +85 °C |
Protection type | IP20 |
Pollution degree (5) | 2 per IEC 61131-2 |
Operating altitude | 0 … 2000 m / 0 … 6562 ft |
Mounting position | horizontal (standing/lying); vertical |
Relative humidity (without condensation) | 95 |
Vibration resistance | per IEC 60068-2-6 |
Shock resistance | 15g per IEC 60068-2-27 |
EMC immunity to interference | per EN 61131-2 |
EMC emission of interference | per EN 61131-2 |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
Permissible pollutant concentration H2S at a relative humidity < 75% | 10 |