Quick Links


Place here any module, widget, design or HTML. for example menu, categories

IIDM

750-563 - 2-channel analog output; 0/4 … 20 mA; 16 bits; 6 ... 18 VDC

  • Brand: Wago
  • Product Code: 750-563
Description: This analog output module generates output currents ranging from 0/4 to 20mA or output voltages in the range from 6 to 18V for the field. Output ranges can be configured via WAGO‐I/O‐CHECK or GSD files. The module has two short circuit-proof output channels and enables direct connection of two 2-wire actuators to AO 1 and ground or AO2 and ground. Signals are output via AO 1 or AO 2. In addition, the sense lines from 4-wire actuators can be connected to -Sense AO1 and +Sense AO1 or -Sense AO2 and +Sense AO2. Both output channels have a common ground potential. The output signal is electrically isolated and transmitted with a resolution of 16 bits. Both internal system and field side supply power the module.
Description: This analog output module generates output currents ranging from 0/4 to 20mA or output voltages in the range from 6 to 18V for the field. Output ranges can be configured via WAGO‐I/O‐CHECK or GSD files. The module has two short circuit-proof output channels and enables direct connection of two 2-wire actuators to AO 1 and ground or AO2 and ground. Signals are output via AO 1 or AO 2. In addition, the sense lines from 4-wire actuators can be connected to -Sense AO1 and +Sense AO1 or -Sense AO2 and +Sense AO2. Both output channels have a common ground potential. The output signal is electrically isolated and transmitted with a resolution of 16 bits. Both internal system and field side supply power the module.
  • Available Quantity: 0

$564.80

Technical data

Number of analog outputs

2

Number of Channels

2

Signal type

Current

Voltage

Signal type (current)

0 … 20 mADC; 4 … 20 mADC

Signal type (voltage)

6 … 18 VDC

Signal type (configurable)

yes

Actuator connection

2 x (2-wire, 4-wire)

Resolution [bit]

16

Data width

2 x 16-bit data; 2 x 8-bit control/status (optional)

Load impedance (voltage output)

≥ 1.8 kΩ

Load impedance (current output)

≤ 500 Ω

Conversion time (typ. ≤)

5

Measurement error, reference temperature

25

Measurement error, deviation max (upper-range value) ≤±

0.05

Output error, deviation (max.) of the upper-range value

0.05

Temperature coefficient

< ±100 ppm

Recovery time (typ.)

0.3

Configuration options

WAGO-I/O-CHECK

CODESYS Library

e!COCKPIT

Supply voltage (system)

5 VDC; via data contacts

Current consumption (5 V system supply)

95

Supply voltage (field)

24 VDC (-15 … +20 %); via power jumper contacts (power supply via blade contact; transmission via spring contact)

Isolation

500 V system/field

Number of incoming power jumper contacts

2

Number of outgoing power jumper contacts

2

Current carrying capacity (power jumper contacts)

10

Connection data

Connection technology: inputs / outputs

8 x CAGE CLAMP®

Connection type 1

Inputs/Outputs

Solid conductor

0.08 … 2.5 mm² / 28 … 14 AWG

Fine-stranded conductor

0.08 … 2.5 mm² / 28 … 14 AWG

Strip length

8 … 9 mm / 0.31 … 0.35 inches

Physical data

Width

12 mm / 0.472 inches

Height

100 mm / 3.937 inches

Depth

69.8 mm / 2.748 inches

Depth from upper-edge of DIN-rail

62.6 mm / 2.465 inches

Mechanical data

Mounting type

DIN-35 rail

Material data

Color

light gray

Housing material

Polycarbonate; polyamide 6.6

Fire load

0.954

Weight

51.2

Conformity marking

CE

Environmental requirements

Ambient temperature (operation)

0 … +55 °C

Surrounding air temperature (storage)

-25 … +85 °C

Protection type

IP20

Pollution degree (5)

2 per IEC 61131-2

Operating altitude

0 … 2000 m / 0 … 6562 ft

Mounting position

horizontal (standing/lying); vertical

Relative humidity (without condensation)

95

Vibration resistance

4g per IEC 60068-2-6

Shock resistance

15g per IEC 60068-2-27

EMC immunity to interference

per EN 61131-2, marine applications

EMC emission of interference

per EN 61131-2, marine applications

Exposure to pollutants

Per IEC 60068-2-42 and IEC 60068-2-43

Permissible pollutant concentration H2S at a relative humidity < 75%

10

Permissible pollutant concentration SO 2 at a relative humidity < 75%

25

Manual
  • System Manual WAGO I/O System 750 / 753

    Download
  • 2-channel, 0 / 4-20mA

    Download
  • System Manual Series 750/753

    Download
Bid Text
  • 750-563

    Download
  • 750-563

    Download
System Description
  • 750/753 Series I/O-System ‒ General Product Information

    Download
  • Use in Hazardous Environments

    Download
  • Overview on WAGO-I/O-SYSTEM 750 approvals

    Download
Additional Information
  • Disposal; Electrical and electronic equipment, Packaging

    Download
Application Note CoDeSys 2.3
  • Application Note Library ModuleAccess_01

    Download
Library
  • ModuleAccess_01.lib

    Download
CAD data
  • 2D/3D Models 750-563

    Download
CAE data
  • EPLAN Data Portal 750-563

    Download
  • WSCAD Universe 750-563

    Download
  • ZUKEN Portal 750-563

    Download
Device Driver
  • WAGO USB Service Kabel Treiber / Serie 750 und 857

    Download
Compliance Search
  • Environmental Product Compliance 750-563

    Download