750-606/040-000 - Power Supply; 24 VDC; Diagnostics; Intrinsically safe; Extreme
- Brand: Wago
- Product Code: 750-606/040-000
- Available Quantity: 0
$1,084.00
Notes
Note | General information (e.g., installation regulations) on explosion protection is available in the WAGO I/O System 750 XTR manuals! |
Technical data
Fuse | Electronic |
Power consumption Pmax. | 29 W |
Data width | 2 bits (input voltage failure, fuse triggered) |
Intrinsic safety Ex i | Yes |
Supply voltage (system) | 5 VDC; via data contacts |
Current consumption (5 V system supply) | 7.5 |
Supply voltage (field) | 24 VDC (-25 … +30 %); via power jumper contacts (power supply via CAGE CLAMP® connection; transmission via spring contact); Derating must be observed! |
Power loss Pl | < 5 W |
Rated surge voltage | 1 kV; Rated surge voltage between intrinsically safe and non-intrinsically safe circuits: 1.5 kV (EN 60079-11) |
Number of outgoing power jumper contacts | 2 |
Current carrying capacity (power jumper contacts) | 1 |
Derating | Derating (supply voltage): Ambient temperatures under laboratory conditions: (−25 … +30 %); for −40 … +55 °C: 24 V (−25 … +20 %); for +55 … +70 °C: 24 V (−25 … +10 %); Lower limit in all temperature ranges: −27.5 % (including 15 % residual ripple) |
Marking | ATEX/IECEx: II 3G Ex ec IIC T4 Gc |
Explosion protection
Ex standard | EN/IEC 60079-0, -7, -11 |
Power supply (output) | Uo = 26.8 V (intrinsically safe output voltage per protection level ia); In = 1 A |
Power supply (input) | Un = 24 VDC; Pmax. = 29 W; Um = 253 V |
Connection data
Connection technology: field supply | 2 x CAGE CLAMP® |
Connection type 1 | Field supply |
Solid conductor | 0.25 … 1.5 mm² / 24 … 14 AWG |
Fine-stranded conductor | 0.25 … 1.5 mm² / 24 … 14 AWG |
Strip length | 5 … 6 mm / 0.2 … 0.24 inches |
Physical data
Width | 48 mm / 1.89 inches |
Height | 100 mm / 3.937 inches |
Depth | 70.9 mm / 2.791 inches |
Depth from upper-edge of DIN-rail | 63.7 mm / 2.508 inches |
Mechanical data
Mounting type | DIN-35 rail |
Material data
Color | dark gray |
Housing material | Polycarbonate; polyamide 6.6 |
Fire load | 0.513 |
Weight | 168.3 |
Conformity marking | CE |
Environmental requirements
Ambient temperature (operation) | -40 … +70 °C |
Surrounding air temperature (storage) | -40 … +85 °C |
Protection type | IP20 |
Pollution degree (5) | 2 per IEC 61131-2 |
Operating altitude | Without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.) |
Mounting position | Horizontal (standing/lying); vertical |
Relative humidity (without condensation) | 95 |
Relative humidity (with condensation) | Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation) |
Vibration resistance | Per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3 |
Shock resistance | Per IEC 60068-2-27 (15g/11 ms/half-sine/1,000 shocks; 25g/6 ms/1,000 shocks), EN 61373 |
EMC immunity to interference | Per EN 61000-6-1, -2, EN 61131-2, marine applications, EN 60255-26, EN 60870-2-1, EN 61850-3, IEC 61000-6-5, IEEE 1613, VDEW: 1994 |
EMC emission of interference | Per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3 |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
Permissible pollutant concentration H2S at a relative humidity < 75% | 10 |
Permissible pollutant concentration SO 2 at a relative humidity < 75% | 25 |