Technical data
Number of digital inputs | 4 |
Number of digital outputs | 4 |
Number of Channels | 8 |
Signal type | Voltage |
Signal type (voltage) | 24 VDC |
Sensor connection | 4 x (Fail-safe input with test pulse) |
Actuator connection | 4 x (fail-safe output with test pulse) |
Input characteristic | clock sensitive |
Input current per channel for signal (1) typ. | 2.2 |
Output circuit design | Power outputs |
Switching frequency (max.) | 5 Hz; Resistive load |
Switching frequency (max.) (2) | 0.1 Hz; Inductive load per IEC 947-5-1, DC 13 |
Switching frequency (max.) (3) | 5 Hz; Inductive load per IEC 947-5-1, DC 13; with recovery diodes |
Load type of switching frequency | Resistive load |
Configuration options | PROFIsafe address adjustable via DIP switch or engineering software |
Supply voltage (system) | 5 VDC; via data contacts |
Current consumption (5 V system supply) | 55 |
Supply voltage (field) | 24 VDC (-15 … +20 %); via power jumper contacts (power supply via blade contact; transmission via spring contact) |
Isolation | 500 V system/field |
Indicators | LED (A-H) green: Status I1 … I8; LED (I-K) red: internal, external error |
Number of incoming power jumper contacts | 2 |
Number of outgoing power jumper contacts | 2 |
Current carrying capacity (power jumper contacts) | 10 |
Functional safety
Achievable safety classes | 4 x Cat. 2/SIL 2 or 2 x Cat. 4/SIL 3 |
Load reactances (max.) | Capacitive 2 nF; inductive corresponding to DC 13 |
Response times (min. … max.) (inputs) | ton (L->H) = 13 ms … 71 ms; toff (H->L) = 13 ms … 26 ms; plus 2 x local bus runtime; plus 2 x fieldbus runtime; plus PLC runtime |
Response times (max.) (outputs) | ton (L->H) = 13 ms; toff (H->L) = 13 ms; plus 2 x local bus runtime; plus 2 x fieldbus runtime; plus PLC runtime |
Proof test interval | 10 |
Connection data
Connection technology: inputs / outputs | 16 x CAGE CLAMP® |
Connection type 1 | Inputs/Outputs |
Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Strip length | 8 … 9 mm / 0.31 … 0.35 inch |
Physical data
Width | 24 mm / 0.945 inch |
Height | 100 mm / 3.937 inch |
Depth | 67.8 mm / 2.669 inch |
Depth from upper-edge of DIN-rail | 60.6 mm / 2.386 inch |
Mechanical data
Mounting type | DIN-35 rail |
Material data
Color | yellow |
Housing material | Polycarbonate; polyamide 6.6 |
Fire load | 2.889 |
Weight | 101.2 |
Conformity marking | CE |
Environmental requirements
Ambient temperature (operation) | 0 … +55 °C |
Surrounding air temperature (storage) | -25 … +85 °C |
Protection type | IP20 |
Pollution degree (5) | 2 per IEC 61131-2 |
Operating altitude | 0 … 2000 m / 0 … 6562 ft |
Mounting position | horizontal (standing/lying); vertical |
Relative humidity (without condensation) | 95 |
Vibration resistance | per IEC 60068-2-6 |
Shock resistance | 15g per IEC 60068-2-27 |
EMC immunity to interference | per EN 61000-6-2 |
EMC emission of interference | per EN 61000-6-4 |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
Permissible pollutant concentration H2S at a relative humidity < 75% | 10 |
Permissible pollutant concentration SO 2 at a relative humidity < 75% | 25 |