Technical data
Number of digital inputs | 4 |
Number of digital outputs | 4 |
Number of Channels | 8 |
Signal type | Voltage |
Signal type (voltage) | 24 VDC |
Sensor connection | 4 x (Fail-safe input with test pulse) |
Actuator connection | 4 x (Fail-safe output with test pulse) |
Input characteristic | Clock sensitive |
Input characteristic | Type 1 per IEC 61131 |
Input current per channel for signal (1) typ. | 3 |
Output circuit design | Power outputs |
Output current per channel | 2 |
Output current (module) | 8 |
Output current | Short-circuit-protected |
Switching frequency (max.) | 50 Hz; Resistive load |
Switching frequency (max.) (2) | 0.1 Hz; Inductive load |
Capacitive load for each channel | O1 … O4; 47 μF |
Signal frequency (max.) | 50 |
Load type of switching frequency | Resistive load |
Configuration options | PROFIsafe address adjustable via DIP switch or engineering software |
Supply voltage (system) | 5 VDC; via data contacts |
Current consumption (5 V system supply) | 120 |
Supply voltage (field) | 24 VSELV/PELV DC (-25 … +20 %); via power jumper contacts (power supply via blade contact; transmission via spring contact) |
Current consumption, field supply (module with no external load) | 35 |
Indicators | LED (A-D) green/red: Status/Error I1 … I4; LED (I-M) green/red: Status/error O1 … O4; LED (E) red: Group error; LED (F-H) green/red: Diagnostics |
Number of incoming power jumper contacts | 2 |
Number of outgoing power jumper contacts | 2 |
Current carrying capacity (power jumper contacts) | 10 |
Functional safety
Achievable safety classes | SIL 3; Category 4, PLe (two-channel); SIL 2; Category 2; PLd (one-channel) |
Safety standards | IEC 61508-1 … -7; EN ISO 13849-1; EN 62061 |
Interface types according to ZVEI (inputs) | Drain; A, C0, C1, C2, C3 |
Interface types according to ZVEI (outputs) | source; C0, C1, C2, C3, D0, D1, D2, D3 |
Test pulse duration (max.) | 500 |
Test pulse duration (min.) | 0 |
Connection data
Connection technology: inputs / outputs | 16 x CAGE CLAMP® |
Connection type 1 | Inputs/outputs |
Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Strip length | 8 … 9 mm / 0.31 … 0.35 inch |
Physical data
Width | 24 mm / 0.945 inch |
Height | 100 mm / 3.937 inch |
Depth | 67.8 mm / 2.669 inch |
Depth from upper-edge of DIN-rail | 60.6 mm / 2.386 inch |
Mechanical data
Mounting type | DIN-35 rail |
Pluggable connector | Fixed |
Material data
Housing material | Polycarbonate; polyamide 6.6 |
Fire load | 1.931 |
Weight | 101.6 |
Conformity marking | CE |
Environmental requirements
Ambient temperature (operation) | 0 … +55 °C |
Surrounding air temperature (storage) | -25 … +85 °C |
Protection type | IP20 |
Pollution degree (5) | 2 per IEC 61131-2 |
Operating altitude | 0 … 2000 m / 0 … 6562 ft |
Mounting position | Horizontal (standing/lying); vertical |
Relative humidity (without condensation) | 95 |
Vibration resistance | 4g per IEC 60068-2-6 |
Shock resistance | 15g per IEC 60068-2-27 |
EMC immunity to interference | Per EN 61000-6-2, marine applications, EN 61000-6-7 (FS) |
EMC emission of interference | Per EN 61000-6-3, -4; marine applications |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
Permissible pollutant concentration H2S at a relative humidity < 75% | 10 |