750-829 - Controller BACnet MS/TP
- Brand: Wago
- Product Code: 750-829
- Available Quantity: 0
$1,338.00
Notes
Note | The WAGO BACnet Configurator can be downloaded for free at www.wago.com. |
Technical data
Communication | BACnet MS/TP Modbus (TCP, UDP) ETHERNET |
ETHERNET protocols | HTTP BootP DHCP DNS SNTP FTP SNMP SMTP |
Visualization | Web-Visu |
CPU | 32 bits |
Programming languages per IEC 61131-3 | Instruction List (IL) Ladder Diagram (LD) Function Block Diagram (FBD), Continuous Function Chart (CFC) Structured Text (ST) Sequential Function Chart (SFC) |
Programming environment | WAGO-I/O-PRO V2.3 (based on CODESYS V2.3) |
Configuration options | WAGO-I/O-CHECK BACnet Configurator Web-Based Management |
Network length (max.) | limited by IEEE 802.3 specification |
Baud rate | BACnet MS/TP: 38.4 kBd (9600, 19200, 38400*, 57600, 76800, 115200 Bd (per BACnet standard); * Factory setting) |
Bus segment length (max.) | BACnet MS/TP: 1200 m; Depends on baud rate/cable (per BACnet standard) 1200 m at ≤ 76800 baud; 1000 m at > 76800 baud; ETHERNET: 100 m |
Transmission medium (communication/fieldbus) | ETHERNET: Twisted Pair S-UTP, STP; 100 Ω; Cat. 5e |
Program memory | 1024 KB |
Data memory | 1024 KB |
Non-volatile software memory | 32 |
Memory for fieldbus input variables (max.) | 512 |
Memory for fieldbus output variables (max.) | 512 |
Number of modules per node (max.) | 99 |
Number of modules without a bus extension (max.) | 64 |
Input and output process image (fieldbus) max. | 1020 Worte/1020 Worte |
Device-specific | BACnet device profile: B-BC (BACnet building controller); BACnet revision: 1.7 |
Powerfail RTC buffer | 6 days (min.) |
Indicators | LED (LINK/ACT) green: Network connection via ports 1 … 2; LED (MS/BT, NS) red/green: Status of node/BACnet, network; LED (I/O, USR) red/green/orange: Local data bus status, status programmable by user; LED (A, B) green: Status of system power supply, field supply |
Supply voltage (system) | 24 VDC (-25 … +30 %); via pluggable connector (CAGE CLAMP® connection) |
Input current (typ.) at nominal load (24 V) | 500 |
Power supply efficiency (typ.) at nominal load (24 V) | 90 |
Current consumption (5 V system supply) | 450 |
Total current (system supply) | 1,700 |
Supply voltage (field) | 24 VDC (-25 … +30 %); via power jumper contacts |
Current carrying capacity (power jumper contacts) | 10 |
Number of outgoing power jumper contacts | 3 |
Isolation | 500 V system/supply; BACnet MS/TP: 1500 V (per BACnet standard) |
WSPCert certification | in Vorbereitung |
Connection data
Connection technology: communication/fieldbus | BACnet MS/TP: 1 x Male connector; 4-pole; Modbus TCP/UDP: 2 x RJ-45 |
Connection technology: system supply | 2 x CAGE CLAMP® |
Connection technology: field supply | 6 x CAGE CLAMP® |
Connection type 1 | System/field supply |
Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
Connection type 2 | Communication/fieldbus: BACnet MS/TP |
Solid conductor 2 | 0.2 … 2.5 mm² / 24 … 12 AWG |
Fine-stranded conductor 2 | 0.2 … 2.5 mm² / 24 … 12 AWG |
Strip length 2 | 9 … 10 mm / 0.35 … 0.39 inches |
Connection technology: device configuration | 1 x Male connector; 4-pole |
Physical data
Width | 61.5 mm / 2.421 inches |
Height | 100 mm / 3.937 inches |
Depth | 71.9 mm / 2.831 inches |
Depth from upper-edge of DIN-rail | 64.7 mm / 2.547 inches |
Mechanical data
Weight | 168.9 |
Color | light gray |
Housing material | Polycarbonate; polyamide 6.6 |
Conformity marking | CE |
Environmental requirements
Ambient temperature (operation) | 0 … +55 °C |
Surrounding air temperature (storage) | -25 … +85 °C |
Protection type | IP20 |
Pollution degree (5) | 2 per IEC 61131-2 |
Operating altitude | without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.) |
Relative humidity (without condensation) | 95 |
Mounting position | any |
Mounting type | DIN-35 rail |
Vibration resistance | per IEC 60068-2-6 |
Shock resistance | 15g per IEC 60068-2-27 |
EMC immunity to interference | per EN 61000-6-2 |
EMC emission of interference | per EN 61000-6-3 |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
Fire load | 2.866 |
Permissible pollutant concentration H2S at a relative humidity < 75% | 10 |
Permissible pollutant concentration SO 2 at a relative humidity < 75% | 25 |