Quick Links


Place here any module, widget, design or HTML. for example menu, categories

IIDM

750-880/040-000 - Controller ETHERNET; 3rd Generation; SD Card Slot; Extreme

  • Brand: Wago
  • Product Code: 750-880/040-000
Description: The ETHERNET Controller can be used as a programmable controller within ETHERNET networks in conjunction with the WAGO I/O System. The controller supports all digital, analog and specialty modules found within the 750/753 Series, and is suitable for data rates of 10/100 Mbit/s. Two ETHERNET interfaces and an integrated switch allow the fieldbus to be wired in a line topology, eliminating the need for additional network devices, such as switches or hubs. Both interfaces support autonegotiation and Auto-MDI(X). The DIP switch configures the last byte of the IP address and may be used for IP address assignment. The controller supports both MODBUS/TCP and EtherNet/IP for use in industrial environments. It also supports a wide variety of standard ETHERNET protocols for easy integration into IT environments (e.g., HTTP, BootP, DHCP, DNS, SNTP, SNMP, FTP). For telecontrol applications, the 750-880/040-001 Controller supports the IEC 60870-5-101/-103-104, IEC 61850-7 and IEC 61400-25 communication protocols. An integrated Webserver provides user configuration options, while displaying the controllers status information. The IEC 61131-3 programmable controller is multitasking-capable and features a capacitor-backed RTC. A data memory of 1 MB is available. The 750-880 Controller is equipped with a removable memory card slot. A memory card can be used to transfer device parameters or files (e.g., boot files) from one controller to another. The memory card can be accessed via FTP and be used as an additional drive. The device is ideal for operation in extreme environments thanks to: An extended temperature range Greater immunity to impulse voltages and electromagnetic interference Higher vibration and shock resistance
Description: The ETHERNET Controller can be used as a programmable controller within ETHERNET networks in conjunction with the WAGO I/O System. The controller supports all digital, analog and specialty modules found within the 750/753 Series, and is suitable for data rates of 10/100 Mbit/s. Two ETHERNET interfaces and an integrated switch allow the fieldbus to be wired in a line topology, eliminating the need for additional network devices, such as switches or hubs. Both interfaces support autonegotiation and Auto-MDI(X). The DIP switch configures the last byte of the IP address and may be used for IP address assignment. The controller supports both MODBUS/TCP and EtherNet/IP for use in industrial environments. It also supports a wide variety of standard ETHERNET protocols for easy integration into IT environments (e.g., HTTP, BootP, DHCP, DNS, SNTP, SNMP, FTP). For telecontrol applications, the 750-880/040-001 Controller supports the IEC 60870-5-101/-103-104, IEC 61850-7 and IEC 61400-25 communication protocols. An integrated Webserver provides user configuration options, while displaying the controllers status information. The IEC 61131-3 programmable controller is multitasking-capable and features a capacitor-backed RTC. A data memory of 1 MB is available. The 750-880 Controller is equipped with a removable memory card slot. A memory card can be used to transfer device parameters or files (e.g., boot files) from one controller to another. The memory card can be accessed via FTP and be used as an additional drive. The device is ideal for operation in extreme environments thanks to: An extended temperature range Greater immunity to impulse voltages and electromagnetic interference Higher vibration and shock resistance
Technical data

Communication

EtherNet/IP

Modbus (TCP, UDP)

ETHERNET

ETHERNET protocols

HTTP

BootP

DHCP

DNS

SNTP

FTP

SNMP

Visualization

Web-Visu

Web Visu

CPU

32 bits

Programming languages per IEC 61131-3

Instruction List (IL)

Ladder Diagram (LD)

Function Block Diagram (FBD), Continuous Function Chart (CFC)

Structured Text (ST)

Sequential Function Chart (SFC)

Programming environment

WAGO-I/O-PRO V2.3 (based on CODESYS V2.3)

Configuration options

WAGO-I/O-CHECK

Web-Based Management

Baud rate (communication/fieldbus 1)

10/100 Mbit/s

Baud rate

10/100 Mbit/s

Transmission medium (communication/fieldbus)

Twisted Pair S-UTP; 100 Ω; Cat. 5; 100 m maximum cable length

Transmission performance

Class D per EN 50173

Program memory

1024 KB

Data memory

1024 KB

Non-volatile software memory

32

Type of memory card

SD card

Memory card slot

Push-push mechanism; Cover lid (sealable)

Number of modules per node (max.)

64

Input and output process image (fieldbus) max.

1020 Worte/1020 Worte

Indicators

LED (LINK/ACT) green: Network connection via ports 1 … 2; LED (MS, NS) red/green: Status of node, network; LED (I/O, USR) red/green/orange: Local data bus status, status programmable by user; LED (A, B) green: System power supply status, field supply

Derating

Total current for system supply: 1700 mA (ambient (operating) temperature < 60 °C; 1500 mA (ambient (operating) temperature: 60 … 70 °C); Derating (supply voltage): Ambient temperatures under laboratory conditions: (−25 … +30 %); for −40 … +55 °C: 24 V (−25 … +20 %); for +55 … +70 °C: 24 V (−25 … +10 %); Lower limit in all temperature ranges: −27.5 % (including 15 % residual ripple)

Supply voltage (system)

24 VDC; via pluggable connector (CAGE CLAMP® connection); Derating must be observed!

Input current (typ.) at nominal load (24 V)

500

Power supply efficiency (typ.) at nominal load (24 V)

90

Current consumption (5 V system supply)

450

Total current (system supply)

1,700

Supply voltage (field)

24 VDC; Power supply via pluggable connector (CAGE CLAMP® connection); Transmission via power jumper contacts; Derating must be observed!

Current carrying capacity (power jumper contacts)

10

Number of outgoing power jumper contacts

2

Ratings per

IEC/EN 60664-1

Rated surge voltage

1 kV

Connection data

Connection technology: communication/fieldbus

EtherNet/IPTM: 2 x RJ-45; Modbus TCP/UDP: 2 x RJ-45

Connection technology: system supply

2 x CAGE CLAMP®

Connection technology: field supply

4 x CAGE CLAMP®

Connection type 1

System/field supply

Solid conductor

0.25 … 2.5 mm² / 24 … 14 AWG

Fine-stranded conductor

0.25 … 2.5 mm² / 24 … 14 AWG

Strip length

8 … 9 mm / 0.31 … 0.35 inches

Connection technology: device configuration

1 x Male connector; 4-pole

Physical data

Width

61.5 mm / 2.421 inches

Height

100 mm / 3.937 inches

Depth

71.9 mm / 2.831 inches

Depth from upper-edge of DIN-rail

64.7 mm / 2.547 inches

Mechanical data

Weight

167

Color

dark gray

Housing material

Polycarbonate; polyamide 6.6

Conformity marking

CE

Environmental requirements

Ambient temperature (operation)

-40 … +70 °C

Surrounding air temperature (storage)

-40 … +85 °C

Protection type

IP20

Pollution degree (5)

2 per IEC 61131-2

Operating altitude

without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.)

Relative humidity (without condensation)

95

Relative humidity (with condensation)

Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation)

Mounting position

horizontal (standing/lying); vertical

Mounting type

DIN-35 rail

Vibration resistance

per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3, EN 50155; EN 61373

Shock resistance

per IEC 60068-2-27 (15g/11 ms/half-sine/1,000 shocks; 25g/6 ms/1,000 shocks), EN 50155, EN 61373

EMC immunity to interference

Per EN 61000-6-1, -2; EN 61131-2; marine applications; EN 50121-3-2; EN 50121-4, -5; EN 60255-26;
EN 60870-2-1; EN 61850-3; IEC 61000-6-5; IEEE 1613; VDEW: 1994

EMC emission of interference

per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3, EN 50121-3-2, EN 50121-4, -5

Exposure to pollutants

Per IEC 60068-2-42 and IEC 60068-2-43

Fire load

0.317

Permissible pollutant concentration H2S at a relative humidity < 75%

10

Permissible pollutant concentration SO 2 at a relative humidity < 75%

25

Manual
  • System Manual XTR

    Download
  • ETHERNET Controller /XTR

    Download
  • WAGO MODBUS Master Configurator

    Download
Bid Text
  • 750-880/040-000

    Download
  • 750-880/040-000

    Download
Additional Information
  • Disposal; Electrical and electronic equipment, Packaging

    Download
System Description
    Configuration and Commissioning Software
    • (759-316) WAGO Ethernet Settings / Serie 750

      Download
    Firmware
    • 0750-0880/0xx-00x, Controller ETHERNET

      Download
    CAD data
    • 2D/3D Models 750-880/040-000

      Download
    CAE data
    • EPLAN Data Portal 750-880/040-000

      Download
    • WSCAD Universe 750-880/040-000

      Download
    • WSCAD Universe 750-880/040-000

      Download
    • EPLAN Data Portal 750-880/040-000

      Download
    • ZUKEN Portal 750-880/040-000

      Download
    Device Driver
    • WAGO USB Service Kabel Treiber / Serie 750 und 857

      Download
    Device Description File
    • 750-915; EDS-Dateien for EthernetIP / Serie 750, 765 and 767

      Download
    • MIB-Datei für Ethernet-Controller / Serie 750

      Download
    Compliance Search
    • Environmental Product Compliance 750-880/040-000

      Download