Quick Links


Place here any module, widget, design or HTML. for example menu, categories

IIDM

750-469/040-000 - 2-channel analog input; Thermocouple; Adjustable; Extreme

  • Brand: Wago
  • Product Code: 750-469/040-000
Description: This analog input module directly connects to two thermocouples. Internal electrical isolation allows operation of grounded sensors. The module automatically linearizes the entire temperature range. Cold junction compensation mitigates the clamping unit offset voltage over the 0–55°C operating range. A line break is indicated by a red LED. A green LED indicates readiness for operation and error-free communication with the coupler. The shield directly connects to the DIN-rail. The device is ideal for operation in extreme environments thanks to: An extended temperature range Greater immunity to impulse voltages and electromagnetic interference Higher vibration and shock resistance
Description: This analog input module directly connects to two thermocouples. Internal electrical isolation allows operation of grounded sensors. The module automatically linearizes the entire temperature range. Cold junction compensation mitigates the clamping unit offset voltage over the 0–55°C operating range. A line break is indicated by a red LED. A green LED indicates readiness for operation and error-free communication with the coupler. The shield directly connects to the DIN-rail. The device is ideal for operation in extreme environments thanks to: An extended temperature range Greater immunity to impulse voltages and electromagnetic interference Higher vibration and shock resistance
  • Available Quantity: 0

$886.80

Technical data

Number of analog inputs

2

Number of Channels

2

Signal type

Thermocouple

Low voltages

Signal type (configurable)

Yes

Sensor connection

2 x (2-wire)

Data width

2 x 16-bit data; 2 x 8-bit control/status (optional)

Internal resistance

1000

Resolution (over entire range)

0.1 °C

Conversion time (typ. ≤)

320

Measurement error (25 °C)

< ±6 K (voltage input < ±2 K; cold junction compensation < ±4 K)

Temperature coefficient

< ±0.2 K/K

Sensor types

Thermocouple K; Configurable: J, E, S, T, L, N, U, B, R; ±30 mV, ±60 mV, ±120 mV

Temperature range

Sensor-specific

Cold junction compensation

At each pair of terminal blocks

Supply voltage (system)

5 VDC; via data contacts

Current consumption (5 V system supply)

65

Dielectric strength

510 VAC/775 VDC; per EN 60870-2-1

Rated surge voltage

1 kV

Connection data

Connection technology: inputs / outputs

8 x CAGE CLAMP®

Connection type 1

Inputs/outputs

Solid conductor

0.25 … 2.5 mm² / 24 … 14 AWG

Fine-stranded conductor

0.25 … 2.5 mm² / 24 … 14 AWG

Strip length

8 … 9 mm / 0.31 … 0.35 inch

Physical data

Width

12 mm / 0.472 inch

Height

100 mm / 3.937 inch

Depth

67.8 mm / 2.669 inch

Depth from upper-edge of DIN-rail

60.6 mm / 2.386 inch

Mechanical data

Mounting type

DIN-35 rail

Material data

Color

dark gray

Housing material

Polycarbonate; polyamide 6.6

Fire load

0.147

Weight

38.8

Conformity marking

CE

Environmental requirements

Ambient temperature (operation)

-40 … +70 °C

Surrounding air temperature (storage)

-40 … +85 °C

Protection type

IP20

Pollution degree (5)

2 per IEC 61131-2

Operating altitude

Without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.)

Mounting position

Horizontal (standing/lying); vertical

Relative humidity (without condensation)

95

Relative humidity (with condensation)

Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation)

Vibration resistance

Per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3, EN 50155; EN 61373

Shock resistance

Per IEC 60068-2-27 (15g/11 ms/half-sine/1,000 shocks; 25g/6 ms/1,000 shocks), EN 50155, EN 61373

EMC immunity to interference

Per EN 61000-6-1, -2; EN 61131-2; marine applications; EN 50121-3-2; EN 50121-4, -5; EN 60255-26;
EN 60870-2-1; EN 61850-3; IEC 61000-6-5; IEEE 1613; VDEW: 1994

EMC emission of interference

Per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3, EN 50121-3-2, EN 50121-4, -5

Exposure to pollutants

Per IEC 60068-2-42 and IEC 60068-2-43

Permissible pollutant concentration H2S at a relative humidity < 75%

10

Permissible pollutant concentration SO 2 at a relative humidity < 75%

25

Manual
  • System Manual XTR

    Download
  • 2AI Thermocouple, configurable /XTR

    Download
Bid Text
  • 750-469/040-000

    Download
  • 750-469/040-000

    Download
System Description
  • 750 XTR Series I/O-System ‒ General Product Information

    Download
  • Overview on WAGO-I/O-SYSTEM 750 approvals

    Download
Additional Information
  • Disposal; Electrical and electronic equipment, Packaging

    Download
CAD data
  • 2D/3D Models 750-469/040-000

    Download
CAE data
  • EPLAN Data Portal 750-469/040-000

    Download
  • WSCAD Universe 750-469/040-000

    Download
  • ZUKEN Portal 750-469/040-000

    Download
  • EPLAN Data Portal 750-469/040-000

    Download
  • WSCAD Universe 750-469/040-000

    Download
Compliance Search
  • Environmental Product Compliance 750-469/040-000

    Download