750-538 - 2-channel relay output; Potential-free; 2 changeover contacts; Intrinsically safe
- Brand: Wago
- Product Code: 750-538
- Available Quantity: 0
$625.50
Notes
Note | The digital output module must only be operated via 24 VDC Ex i! General information (e.g., installation regulations) on explosion protection is available in the WAGO I/O System 750 manuals! |
Technical data
Number of digital outputs | 2 |
Number of Channels | 2 |
Signal type | Voltage |
Signal type (voltage) | 100 VAC; 30 VDC |
Actuator connection | 2 x (2-wire) |
Output circuit design | 2 changeover contacts Relay |
Output characteristic | potential-free |
Switching frequency (max.) | 0.3 Hz |
Load type | Resistive, inductive, lamp load |
Switching voltage (max.) | 100 VAC, 30 VDC |
Switching current (max.) | 0.5 |
Switching current (note) | 0.5 A at 100 VAC; 1 A at 30 VDC |
Switching voltage (min.) | 0.1 |
Switching current (min.) | 0.01 |
Power consumption Pmax. | 0.8 W |
Switching power | 50 VA / 30 W |
Pull-in time (max.) | 4 |
Drop-out time (max.) | 4 |
Electrical switching operations (min.) (at max. resistive load) | 100 x 10³ switching operations |
Mechanical switching operations (min.) (at max. resistive load) | 100 x 10⁶ switching operations |
Output data width (internal) max. | 2 |
Intrinsic safety Ex i | yes |
Supply voltage (system) | 5 VDC; via data contacts |
Current consumption (5 V system supply) | 26 |
Supply voltage (field) | 24 VDC; (Ex i power supply: UO = max. 27.3 V); via power jumper contacts (power supply via blade contact; transmission via spring contact) |
Current consumption, field supply (module with no external load) | 24 |
Power loss Pl | 0.8 W |
Isolation | 300 VAC system/field |
Number of incoming power jumper contacts | 2 |
Number of outgoing power jumper contacts | 2 |
Current carrying capacity (power jumper contacts) | 1 |
Marking | ATEX/IECEx: II 3 (1) G Ex ec [ia Ga] IIC T4 Gc; II (1) D [Ex ia Da] IIIC; I (M1) [Ex ia Ma] I |
Explosion protection
Ex standard | EN IEC 60079-0, -7, -11 |
Safety-relevant data (circuit) | Relay output: Ui = 30 VDC; Ii = 1 A; Pi = 30 W; Ui = 100 VAC; Ii = 0.5 A; Pi = 50 VA; Li = negligibly small; Ci = negligibly small |
Connection data
Connection technology: inputs / outputs | 8 x CAGE CLAMP® |
Connection type 1 | Inputs/Outputs |
Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
Physical data
Width | 12 mm / 0.472 inches |
Height | 100 mm / 3.937 inches |
Depth | 67.8 mm / 2.669 inches |
Depth from upper-edge of DIN-rail | 60.6 mm / 2.386 inches |
Mechanical data
Mounting type | DIN-35 rail |
Material data
Color | blue |
Contact material | Ag alloy (with gold flash) |
Housing material | Polycarbonate; polyamide 6.6 |
Fire load | 0.874 |
Weight | 49.1 |
Conformity marking | CE |
Environmental requirements
Ambient temperature (operation) | 0 … +55 °C |
Surrounding air temperature (storage) | -25 … +85 °C |
Protection type | IP20 |
Pollution degree (5) | 2 per IEC 61131-2 |
Operating altitude | 0 … 2000 m / 0 … 6562 ft |
Mounting position | horizontal (standing/lying); vertical |
Relative humidity (without condensation) | 95 |
Vibration resistance | 4g per IEC 60068-2-6 |
Shock resistance | 15g per IEC 60068-2-27 |
EMC immunity to interference | per EN 61000-6-2, marine applications |
EMC emission of interference | per EN 61000-6-3, marine applications |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
Permissible pollutant concentration H2S at a relative humidity < 75% | 10 |
Permissible pollutant concentration SO 2 at a relative humidity < 75% | 25 |