750-633 - Up/Down Counter; Intrinsically safe
- Brand: Wago
- Product Code: 750-633
- Available Quantity: 0
$889.80
Notes
Note | The up/down counter must only be operated via 24 VDC Ex i XTR power supply! General information (e.g., installation regulations) on explosion protection is available in the WAGO I/O System 750 manuals! |
Technical data
Number of digital outputs | 1 |
Number of counters | 1 |
Counter depth | 32 |
Sensor supply UV | 8.2 |
Input filter | 10 µs |
Open-circuit voltage | 8.2 |
Output voltage | 24 VDC |
Short-circuit current | 8.2 mA (+/- 5 %) |
Signal current (0) | 1.2 |
Signal current (1) | 2.1 |
Switching hysteresis | 0.2 |
Switching frequency | 20 Hz … 50 kHz |
Input resistance (max.) | 1000 |
Internal resistance Ri | 285 |
Power consumption Pmax. | 2.2 W (sensor load: 8.2 mA + actuator load: 45 mA) |
Data width | 1 x 32-bit data, 1 x 8-bit status/diagnostics |
Intrinsic safety Ex i | yes |
Supply voltage (system) | 5 VDC; via data contacts |
Current consumption (5 V system supply) | 25 |
Supply voltage (field) | 24 VDC; (Ex i power supply: UO = max. 27.3 V); via power jumper contacts (power supply via blade contact; transmission via spring contact) |
Current consumption, field supply (module with no external load) | 31 |
Power loss Pl | 1.7 W (sensor load: 8.2 mA + actuator load: 45 mA) |
Isolation | 300 VAC system/field |
Number of incoming power jumper contacts | 2 |
Number of outgoing power jumper contacts | 2 |
Current carrying capacity (power jumper contacts) | 1 |
Marking | ATEX/IECEx: II 3 (1) G Ex ec [ia Ga] IIC T4 Gc; II (1) D [Ex ia Da] IIIC; I (M1) [Ex ia Ma] I |
Explosion protection
Ex standard | EN IEC 60079-0, -7, -11 |
Safety data (input) | Uo = 12 V; Io = 13.5 mA; Po = 40.5 mW; Linear characteristic curve |
Reactances of Ex ia IIC inputs | Lo = 100 mH; Co = 1.4 µF |
Reactances of Ex ia IIB inputs | Lo = 100 mH; Co = 9 µF |
Reactances of Ex ia IIA inputs | Lo = 100 mH; Co = 36 µF |
Reactances of Ex ia I inputs | Lo = 100 mH; Co = 38 µF |
Safety data (output) | Uo = 27.3 V; Io = 103 mA; Po = 703 mW; Linear characteristic curve |
Reactances of Ex ia IIC output | Lo = 0.5 mH; Co = 88 nF |
Reactances of Ex ia IIB output | Lo = 10 mH; Co = 683 nF |
Reactances of Ex ia IIA output | Lo = 18 mH; Co = 2.2 µF |
Reactances of Ex ia I output | Lo = 26 mH; Co = 3.6 µF |
Reactances (note) | Reactances without accounting for the concurrence of capacitance (Co) and inductance (Lo) |
Connection data
Connection technology: inputs / outputs | 16 x CAGE CLAMP® |
Connection type 1 | Inputs/Outputs |
Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
Physical data
Width | 24 mm / 0.945 inches |
Height | 100 mm / 3.937 inches |
Depth | 67.8 mm / 2.669 inches |
Depth from upper-edge of DIN-rail | 60.6 mm / 2.386 inches |
Mechanical data
Mounting type | DIN-35 rail |
Material data
Color | blue |
Housing material | Polycarbonate; polyamide 6.6 |
Fire load | 1.683 |
Weight | 88.2 |
Conformity marking | CE |
Environmental requirements
Ambient temperature (operation) | 0 … +55 °C |
Surrounding air temperature (storage) | -25 … +85 °C |
Protection type | IP20 |
Pollution degree (5) | 2 per IEC 61131-2 |
Operating altitude | 0 … 2000 m / 0 … 6562 ft |
Mounting position | horizontal (standing/lying); vertical |
Relative humidity (without condensation) | 95 |
Vibration resistance | 4g per IEC 60068-2-6 |
Shock resistance | 15g per IEC 60068-2-27 |
EMC immunity to interference | per EN 61000-6-2, marine applications |
EMC emission of interference | per EN 61000-6-3, marine applications |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
Permissible pollutant concentration H2S at a relative humidity < 75% | 10 |
Permissible pollutant concentration SO 2 at a relative humidity < 75% | 25 |