Quick Links


Place here any module, widget, design or HTML. for example menu, categories

IIDM

750-633/040-000 - Up/Down Counter; Intrinsically safe; Extreme

  • Brand: Wago
  • Product Code: 750-633/040-000
Description: This counter records binary pulse signals with NAMUR-compliant levels and transmits the counter state to the fieldbus system. The counting direction in “up/down counter” mode can be set using the U/D input. A control byte sets or resets the counter and digital output (DO). Additionally, a limit value can be set at which the DO output is activated when this value is exceeded. The output is short-circuit-proof. Operating modes: Up counter with enable input Up/Down Counter Frequency counter Peak-time counter Indicators: Green LED (Up/Down + CLK + DO status) Red LED (Up/Down + CLK error status) Field and system levels are electrically isolated. The device is ideal for operation in extreme environments thanks to: An extended temperature range Greater immunity to impulse voltages and electromagnetic interference Higher vibration and shock resistance
Description: This counter records binary pulse signals with NAMUR-compliant levels and transmits the counter state to the fieldbus system. The counting direction in “up/down counter” mode can be set using the U/D input. A control byte sets or resets the counter and digital output (DO). Additionally, a limit value can be set at which the DO output is activated when this value is exceeded. The output is short-circuit-proof. Operating modes: Up counter with enable input Up/Down Counter Frequency counter Peak-time counter Indicators: Green LED (Up/Down + CLK + DO status) Red LED (Up/Down + CLK error status) Field and system levels are electrically isolated. The device is ideal for operation in extreme environments thanks to: An extended temperature range Greater immunity to impulse voltages and electromagnetic interference Higher vibration and shock resistance
Notes

Note

The up/down counter must only be operated via 24 VDC Ex i XTR power supply (750-606/040-000)!

General information (e.g., installation regulations) on explosion protection is available in the WAGO I/O System 750 XTR manuals!

Technical data

Number of digital outputs

1

Number of counters

1

Counter depth

32

Sensor supply UV

8.2

Input filter

10 µs

Open-circuit voltage

8.2

Output voltage

24 VDC

Short-circuit current

8.2 mA (+/- 5 %)

Signal current (0)

1.2

Signal current (1)

2.1

Switching hysteresis

0.2

Switching frequency

20 Hz … 50 kHz

Input resistance (max.)

1000

Internal resistance Ri

285

Power consumption Pmax.

2.2 W (sensor load: 8.2 mA + actuator load: 45 mA)

Data width

1 x 32-bit data, 1 x 8-bit status/diagnostics

Intrinsic safety Ex i

yes

Supply voltage (system)

5 VDC; via data contacts

Current consumption (5 V system supply)

25

Supply voltage (field)

24 VDC; (Ex i XTR power supply: UO = max. 26.8 V); via power jumper contacts (power supply via blade contact; transmission via spring contact)

Current consumption, field supply (module with no external load)

31

Power loss Pl

1.7 W (sensor load: 8.2 mA + actuator load: 45 mA)

Isolation

300 VAC system/field

Rated surge voltage

1 kV; Rated surge voltage between intrinsically safe and non-intrinsically safe circuits: 1.5 kV (EN 60079-11)

Number of incoming power jumper contacts

2

Number of outgoing power jumper contacts

2

Current carrying capacity (power jumper contacts)

1

Marking

ATEX/IECEx: II 3 (1) G Ex ec [ia Ga] IIC T4 Gc; II (1) D [Ex ia Da] IIIC; I (M1) [Ex ia Ma] I

Explosion protection

Ex standard

EN/IEC 60079-0, -7, -11

Safety data (input)

Uo = 12 V; Io = 13.3 mA; Po = 40.4 mW; Linear characteristic curve

Reactances of Ex ia IIC inputs

Lo = 100 mH; Co = 1.41 µF

Reactances of Ex ia IIB inputs

Lo = 100 mH; Co = 9 µF

Reactances of Ex ia IIA inputs

Lo = 100 mH; Co = 36 µF

Reactances of Ex ia I inputs

Lo = 100 mH; Co = 35 µF

Safety data (output)

Uo = 26.8 V; Io = 96.69 mA; Po = 674.83 mW; Linear characteristic curve

Reactances of Ex ia IIC output

Lo = 1.3 mH; Co = 0.091 µF

Reactances of Ex ia IIB output

Lo = 13 mH; Co = 0.719 µF

Reactances of Ex ia IIA output

Lo = 23 mH; Co = 2.369 µF

Reactances of Ex ia I output

Lo = 33 mH; Co = 3.849 µF

Reactances (note)

Reactances without accounting for the concurrence of capacitance (Co) and inductance (Lo)

Connection data

Connection technology: inputs / outputs

16 x CAGE CLAMP®

Connection type 1

Inputs/Outputs

Solid conductor

0.25 … 2.5 mm² / 24 … 14 AWG

Fine-stranded conductor

0.25 … 2.5 mm² / 24 … 14 AWG

Strip length

8 … 9 mm / 0.31 … 0.35 inches

Physical data

Width

24 mm / 0.945 inches

Height

100 mm / 3.937 inches

Depth

67.8 mm / 2.669 inches

Depth from upper-edge of DIN-rail

60.6 mm / 2.386 inches

Mechanical data

Mounting type

DIN-35 rail

Material data

Color

blue

Housing material

Polycarbonate; polyamide 6.6

Fire load

1.249

Weight

88.1

Conformity marking

CE

Environmental requirements

Ambient temperature (operation)

-40 … +70 °C

Surrounding air temperature (storage)

-40 … +85 °C

Protection type

IP20

Pollution degree (5)

2 per IEC 61131-2

Operating altitude

without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.)

Mounting position

horizontal (standing/lying); vertical

Relative humidity (without condensation)

95

Relative humidity (with condensation)

Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation)

Vibration resistance

per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3

Shock resistance

per IEC 60068-2-27 (15g/11 ms/half-sine/1,000 shocks; 25g/6 ms/1,000 shocks), EN 61373

EMC immunity to interference

per EN 61000-6-1, -2, EN 61131-2, marine applications, EN 60255-26, EN 60870-2-1, EN 61850-3, IEC 61000-6-5, IEEE 1613, VDEW: 1994

EMC emission of interference

per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3

Exposure to pollutants

Per IEC 60068-2-42 and IEC 60068-2-43

Permissible pollutant concentration H2S at a relative humidity < 75%

10

Permissible pollutant concentration SO 2 at a relative humidity < 75%

25

Data sheet
  • 750-633/040-000, Up/Down Counter Ex i XTR

    Download
Manual
  • System Manual XTR

    Download
  • Up/Down Counter Ex i /XTR

    Download
  • System Manual Series 750/753

    Download
Bid Text
  • 750-633/040-000

    Download
  • 750-633/040-000

    Download
System Description
  • Overview on WAGO-I/O-SYSTEM 750 approvals

    Download
  • Intrinsically Safe XTR Modules ‒ General Product Information

    Download
Additional Information
  • Disposal; Electrical and electronic equipment, Packaging

    Download
CAD data
  • 2D/3D Models 750-633/040-000

    Download
CAE data
  • EPLAN Data Portal 750-633/040-000

    Download
  • EPLAN Data Portal 750-633/040-000

    Download
  • ZUKEN Portal 750-633/040-000

    Download