750-880/040-001 - Controller ETHERNET; 3rd Generation; SD Card Slot; Telecontrol technology; Extreme
- Brand: Wago
- Product Code: 750-880/040-001
Technical data
Communication | EtherNet/IP Modbus (TCP, UDP) ETHERNET Telecontrol protocols |
ETHERNET protocols | HTTP BootP DHCP DNS SNTP FTP SNMP |
Telecontrol protocols | IEC 60870-5-101/-103/-104 IEC 61400-25 IEC 61850-7 DNP3 |
Visualization | Web-Visu Web Visu |
CPU | 32 bits |
Programming languages per IEC 61131-3 | Instruction List (IL) Ladder Diagram (LD) Function Block Diagram (FBD), Continuous Function Chart (CFC) Structured Text (ST) Sequential Function Chart (SFC) |
Programming environment | WAGO-I/O-PRO V2.3 (based on CODESYS V2.3) |
Configuration options | WAGO-I/O-CHECK Web-Based Management CODESYS Library |
Baud rate (communication/fieldbus 1) | 10/100 Mbit/s |
Baud rate | 10/100 Mbit/s |
Transmission medium (communication/fieldbus) | Twisted Pair S-UTP; 100 Ω; Cat. 5; 100 m maximum cable length |
Transmission performance | Class D per EN 50173 |
Program memory | 1024 KB |
Data memory | 1024 KB |
Non-volatile software memory | 32 |
Type of memory card | SD card |
Memory card slot | Push-push mechanism; Cover lid (sealable) |
Number of modules per node (max.) | 64 |
Input and output process image (fieldbus) max. | 1020 Worte/1020 Worte |
Indicators | LED (LINK/ACT) green: Network connection via ports 1 … 2; LED (MS, NS) red/green: Status of node, network; LED (I/O, USR) red/green/orange: Local data bus status, status programmable by user; LED (A, B) green: System power supply status, field supply |
Derating | Total current for system supply: 1700 mA (ambient (operating) temperature < 60 °C; 1500 mA (ambient (operating) temperature: 60 … 70 °C); Derating (supply voltage): Ambient temperatures under laboratory conditions: (−25 … +30 %); for −40 … +55 °C: 24 V (−25 … +20 %); for +55 … +70 °C: 24 V (−25 … +10 %); Lower limit in all temperature ranges: −27.5 % (including 15 % residual ripple) |
Supply voltage (system) | 24 VDC; via pluggable connector (CAGE CLAMP® connection); Derating must be observed! |
Input current (typ.) at nominal load (24 V) | 500 |
Power supply efficiency (typ.) at nominal load (24 V) | 90 |
Current consumption (5 V system supply) | 450 |
Total current (system supply) | 1,700 |
Supply voltage (field) | 24 VDC; Power supply via pluggable connector (CAGE CLAMP® connection); Transmission via power jumper contacts; Derating must be observed! |
Current carrying capacity (power jumper contacts) | 10 |
Number of outgoing power jumper contacts | 2 |
Ratings per | IEC/EN 60664-1 |
Rated surge voltage | 1 kV |
Connection data
Connection technology: communication/fieldbus | EtherNet/IPTM: 2 x RJ-45; Modbus TCP/UDP: 2 x RJ-45; Telecontrol protocol IEC 60870-5-101/-103: 1 x Serial interface via I/O module; Telecontrol protocol IEC 60870-5-104: 1 x RJ-45; Telecontrol protocol IEC 61850: 1 x RJ-45; Telecontrol protocol DNP3: 1 x RJ-45 |
Connection technology: system supply | 2 x CAGE CLAMP® |
Connection technology: field supply | 4 x CAGE CLAMP® |
Connection type 1 | System/field supply |
Solid conductor | 0.25 … 2.5 mm² / 24 … 14 AWG |
Fine-stranded conductor | 0.25 … 2.5 mm² / 24 … 14 AWG |
Strip length | 8 … 9 mm / 0.31 … 0.35 inches |
Connection technology: device configuration | 1 x Male connector; 4-pole |
Physical data
Width | 61.5 mm / 2.421 inches |
Height | 100 mm / 3.937 inches |
Depth | 71.9 mm / 2.831 inches |
Depth from upper-edge of DIN-rail | 64.7 mm / 2.547 inches |
Mechanical data
Weight | 154.5 |
Color | dark gray |
Housing material | Polycarbonate; polyamide 6.6 |
Conformity marking | CE |
Environmental requirements
Ambient temperature (operation) | -40 … +70 °C |
Surrounding air temperature (storage) | -40 … +85 °C |
Protection type | IP20 |
Pollution degree (5) | 2 per IEC 61131-2 |
Operating altitude | without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.) |
Relative humidity (without condensation) | 95 |
Relative humidity (with condensation) | Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation) |
Mounting position | horizontal (standing/lying); vertical |
Mounting type | DIN-35 rail |
Vibration resistance | per IEC 60068-2-6 (acceleration: 5g), EN 60870-2-2, IEC 60721-3-1, -3, EN 50155; EN 61373 |
Shock resistance | per IEC 60068-2-27 (15g/11 ms/half-sine/1,000 shocks; 25g/6 ms/1,000 shocks), EN 50155, EN 61373 |
EMC immunity to interference | Per EN 61000-6-1, -2; EN 61131-2; marine applications; EN 50121-3-2; EN 50121-4, -5; EN 60255-26; |
EMC emission of interference | per EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3, EN 50121-3-2, EN 50121-4, -5 |
Exposure to pollutants | Per IEC 60068-2-42 and IEC 60068-2-43 |
Fire load | 0.317 |
Permissible pollutant concentration H2S at a relative humidity < 75% | 10 |
Permissible pollutant concentration SO 2 at a relative humidity < 75% | 25 |