Quick Links


Place here any module, widget, design or HTML. for example menu, categories

IIDM

788-615 - Relay module; Nominal input voltage: 115 VAC; 2 changeover contacts; Limiting continuous current: 8 A; with gold contacts; Red status indicator; Module width: 15 mm; 2,50 mm²; gray

  • Brand: Wago
  • Product Code: 788-615
Description:
  • Available Quantity: 0

$39.16

Technical data
Control circuit

Nominal input voltage UN

AC 115 V

Input voltage range

±10 %

Nominal input current at UN

8.2 mA

Load circuit

Number of changeover contacts

2

Contact material (relay)

AgNi + Au

Limiting continuous current

8 A

Switching voltage (max.)

AC 250 V

Switching power (resistive) max.

AC 2000 VA; DC (see load limit curve)

Switching capacity

AC-15: 3 A / AC 250 V; DC-13: 2 A / DC 24 V

Recommended minimum load

5 V / 2 mA / 50 mW

Pull-in time (typ.)

7

Drop-out time (typ.)

3

Bounce time (typ.)

6

Electrical life (NO; resistive load; 23 °C)

100 x 10³ switching operations

Mechanical life

30 x 10⁶ switching operations

Switching frequency with/without load (max.)

10 min-1 / 1200 min-1

Signaling

Status indicator

Red LED

Safety and protection

Rated voltage

250

Rated surge voltage

4

Pollution degree

3

Dielectric strength (control/load circuit) (AC, 1 min)

5 kVrms

Dielectric strength (open contact) (AC, 1 min)

1 kVrms

Dielectric strength (load/load circuit) (AC, 1 min)

2.5 kVrms

Safety information 1

A separator plate (e.g., 209-191) must be used for voltages greater than 250 V between adjacent relay modules and for compliance with the reinforced insulation requirements.

Protection type

IP20

Notes

Safety information 1

A separator plate (e.g., 209-191) must be used for voltages greater than 250 V between adjacent relay modules and for compliance with the reinforced insulation requirements.

Note

  • Reinforced insulation between coil and contacts
  • To prevent damaging the gold layer, 30 VDC switching voltages and 50 mA currents must not be exceeded. Higher switching power eventually evaporates the gold layer. The resulting deposits in the housing may reduce service life.
  • To protect the relay coils and contacts, inductive loads must be dampened with an effective protection circuit.

Connection data

Connection technology

Push-in CAGE CLAMP®

Solid conductor

0.34 … 2.5 mm² / 22 … 14 AWG

Fine-stranded conductor

0.34 … 2.5 mm² / 22 … 14 AWG

Strip length

9 … 10 mm / 0.35 … 0.39 inches

Physical data

Width

15 mm / 0.591 inches

Height

86 mm / 3.386 inches

Depth from upper-edge of DIN-rail

54 mm / 2.126 inches

Mechanical data

Mounting type

DIN-35 rail

Material data

Color

gray

Fire load

0.642

Weight

47.7

Environmental requirements

Ambient temperature (operation at UN)

-40 … 70 °C

Ambient temperature UL (operation at UN)

-40 … 50 °C

Surrounding air temperature (storage)

-40 … +70 °C

Processing temperature

-25 … +50 °C

Standards and specifications

Standards/specifications

EN 61010-2-201

EN 61810-1

EN 61373

UL 508

DNV

Basic relay

WAGO Basic Relay

788-177

Bid Text
  • 788-615

    Download
  • 788-615

    Download
Instruction Leaflet
  • Sockets with Elementary Relay/ SSR

    Download
Additional Information
  • Disposal; Electrical and electronic equipment, Packaging

    Download
CAD data
  • 2D/3D Models 788-615

    Download
CAE data
  • EPLAN Data Portal 788-615

    Download
  • WSCAD Universe 788-615

    Download
  • ZUKEN Portal 788-615

    Download
Compliance Search
  • Environmental Product Compliance 788-615

    Download