789-312 - Relay module; Nominal input voltage: 24 VDC; 2 changeover contacts; Limiting continuous current: 8 A; Red status indicator; Module width: 18 mm; 2,50 mm²; gray
- Brand: Wago
- Product Code: 789-312
- Available Quantity: 0
$66.06
Technical data
Control circuit
Nominal input voltage UN | DC 24 V |
Input voltage range | -15 … +10 % |
Nominal input current at UN | 21 mA |
Load circuit
Number of changeover contacts | 2 |
Contact material (relay) | AgNi 90/10 |
Limiting continuous current | 8 A |
Inrush current (resistive) max. | (AC) 15 A / 4 s |
Switching voltage (max.) | AC 250 V |
Switching power (resistive) max. | AC 2000 VA; DC (see load limit curve) |
Recommended minimum load | 12 V / 10 mA |
Pull-in time (typ.) | 8 |
Drop-out time (typ.) | 6 |
Bounce time (typ.) | 6 |
Mechanical life | 30 x 106 switching operations |
Signaling
Status indicator | Red LED |
Safety and protection
Rated voltage | 250 |
Rated surge voltage | 4 |
Pollution degree | 2 |
Dielectric strength (control/load circuit) (AC, 1 min) | 5 kVrms |
Dielectric strength (open contact) (AC, 1 min) | 1 kVrms |
Dielectric strength (load/load circuit) (AC, 1 min) | 2.5 kVrms |
Protection type | IP20 |
Notes
Note | To protect the relay coils and contacts, inductive loads must be dampened with an effective protection circuit. |
Connection data
Connection technology | CAGE CLAMP® |
Solid conductor | 0.2 … 2.5 mm² / 24 … 14 AWG |
Fine-stranded conductor | 0.2 … 2.5 mm² / 24 … 14 AWG |
Strip length | 9 … 10 mm / 0.35 … 0.39 inch |
Physical data
Width | 17.5 mm / 0.689 inch |
Height | 90 mm / 3.543 inch |
Depth from upper-edge of DIN-rail | 55 mm / 2.165 inch |
Mechanical data
Mounting type | DIN-35 rail |
Material data
Color | gray |
Fire load | 2.934 |
Weight | 55 |
Environmental requirements
Ambient temperature (operation at UN) | -25 … 40 °C |
Surrounding air temperature (storage) | -40 … +85 °C |
Processing temperature | -25 … +50 °C |
Standards and specifications
Standards/specifications | EN61010-2-201 |