101056640 - IFL 20-400-10/01YG
- Brand: Schmersal
- Product Code: 101056640
- 1 Cable entry PG9 x 1.5
- Thermoplastic enclosure
- AC 2-wire
- Double-insulated
- Wiring compartment
- Design Ø 40 mm
Data
Ordering data
Product type description | IFL 20-400-10/01YG |
Article number (order number) | 101056640 |
EAN (European Article Number) | 4030661020594 |
eCl@ss number, version 9.0 | 27-27-01-01 |
eCl@ss number, version 11.0 | 27-27-01-01 |
ETIM number, version 7.0 | EC002714 |
ETIM number, version 6.0 | EC002714 |
Approvals - Standards
Certificates | CCC |
General data
Standards | DIN VDE 0660-208 IEC/EN 60947-5-2 |
Housing construction form | Cylinder smooth |
Installation conditions (mechanical) | not flush |
Enclosure material | Plastic |
Active area | Plastic |
Material of the terminal fixing | Plastic |
Gross weight | 195 g |
General data - Features
Integral system diagnostics, status | Yes |
Number of cable wires | 2 |
Mechanical data - Switching distances according EN IEC 60947-5-3
Switching distance | 20 mm |
Mechanical data - Connection technique
Type of connection | Screw connection |
Cable section, maximum | 2 x 1.5 mm² |
Mechanical data - Dimensions
Diameter of sensor | 40 mm |
Length of sensor | 108 mm |
Width of sensor | 40 mm |
Height of sensor | 57 mm |
Ambient conditions
Degree of protection | IP65 |
Ambient temperature, minimum | -25 °C |
Ambient temperature, maximum | +70 °C |
Protection class | II |
Ambient conditions - Insulation values
Rated impulse withstand voltage U | 4 kV |
Electrical data
Voltage type | AC (alternating current) |
Rated supply frequency, minimum | 45 Hz |
Rated supply frequency, maximum | 65 Hz |
Operating voltage, minimum | 15 V |
Operating voltage, maximum | 250 V |
Operating current, minimum | 10 mA |
Operating current | 500 mA |
Switching element | NO contact or NC contact |
Protection circuit integrated | inductive interference protection |
Switching frequency, approx. | 10 Hz |
Electrical data - Digital Output
Voltage drop U | 4.5 V |
Current at Voltage drop U | 0.2 A |
Design of switching elements | Two-wire |
Leakage current, maximum I | 1 mA |
Status indication
Note (Integral System Diagnostics, status ) | yellow LED |
Scope of delivery
Note (scope of delivery, number and type) | Clamp H 40 is included in delivery |
Note
Note (General) | Programmable by repositioning the plug-in jumper at the terminal screws |