2857-533/000-001 - Threshold value switches; RTD sensors; 1 make contact; Digital output; Configuration via software; Supply voltage: 24 VDC; 12.5 mm module width; Railway

  • Brand: Wago
  • Product Code: 2857-533/000-001
Description: Short description: WAGOs RTD threshold value switch for RTD sensors, potentiometers and resistors monitors and reports signals for up to two switching thresholds. Features: Both digital signal output and relay with make contact react to configured measurement range limits (on/off switching delay and threshold value switch function can be configured with up to two threshold values). Configurable RTD factor Adjustable software filter Input/output response simulation via configuration display Safe three-way isolation with 4 kV test voltage per EN 61010-1 For railway applications
Description: Short description: WAGOs RTD threshold value switch for RTD sensors, potentiometers and resistors monitors and reports signals for up to two switching thresholds. Features: Both digital signal output and relay with make contact react to configured measurement range limits (on/off switching delay and threshold value switch function can be configured with up to two threshold values). Configurable RTD factor Adjustable software filter Input/output response simulation via configuration display Safe three-way isolation with 4 kV test voltage per EN 61010-1 For railway applications
  • Available Quantity: 0

$416.30

Technical data
Configuration

Configuration options

WAGO Interface Configuration Software

WAGO Configuration Display

WAGO Interface Configuration Software

WAGO Configuration Display

Input

Input signal type

Potentiometer

Resistance

RTD sensors

Potentiometers

Resistor

Input – RTD sensors

Sensor types (RTD)

Pt100

Pt200

Pt500

Pt1000

Pt5000

Pt10000

Pt10 … Pt20000

Sensor connection

2-wire; 3-wire; 4-wire; differential

Sensor power supply (RTD) max.

≤ 0.5 mA

Temperature measurement range (RTD)

-200 … 850°C

Input – resistors

Input range (resistor)

0 … 100 kΩ

Input range (potentiometer)

0 … 100 kΩ

Output – digital

Switching voltage (DO) max.

Supply voltage (applied): −0.3 V

Continuous current (DO) max.

100 mA (no internal restriction)

Number of switching thresholds (DO)

1 or 2 (adjustable)

Configurable rise/fall delay time (DO)

0 … 60 s (via software)

Output – relay

Number of make/switch-on contacts

1

Contact material (relay)

AgNi + Au

Switching voltage (max.)

AC 250 V

Limiting continuous current (relay; module assembly)

6 A (≤ 60 °C); 3 A (60 … 70 °C)

Dielectric strength (open contact) (AC, 1 min)

1 kVrms

Pull-in time (typ.)

8

Drop-out time (typ.)

4

Bounce time (typ.)

8

Number of switching thresholds (relay)

1 or 2 (adjustable)

Configurable rise/fall delay time (relay)

0 … 60 s (via software)

Signal processing

Software filter (adjustable)

Moving average value (filter level: 30)

Step response (typ.)

60 ms (2-wire); 360 ms (3-wire); 540 ms (4-wire); 360 ms (Potentiometer)

Measurement error

Transmission error (max.)

± 1 K

Temperature coefficient

≤ 0.01 %/K

Supply

Power supply type

24 VDC

Nominal supply voltage US

DC 24 V (SELV)

Supply voltage range

±30 %

Current consumption at nominal supply voltage

≤ 40 mA (+ IDO)

Notes

Note

This product is supplied with 24 VDC, which can be commoned using lateral push-in type jumper bars: (6.1) US+ (BR) and (6.2) GND 2 (BR). With this variant, it is necessary to ensure that the maximum permissible total current of 2 A is not exceeded.

Safety and protection

Rated voltage of the measurement circuit connections per EN 61010-2-030

AC 300 V

Note on insulation parameters

The digital output (DO) is at the potential of the supply.

Temperature sensors are not intended for use in dangerous circuits, provided the external temperature sensors used do not have basic insulation in accordance with EN 61010-1 (300 VAC; overvoltage category II; pollution degree 2).

The digital output (DO) is at the potential of the supply

Protection type

IP20

Connection data

Connection technology

Push-in CAGE CLAMP®

WAGO connector

picoMAX® 5.0

Solid conductor

0.2 … 2.5 mm² / 24 … 12 AWG

Fine-stranded conductor

0.2 … 2.5 mm² / 24 … 12 AWG

Strip length

9 … 10 mm / 0.35 … 0.39 inch

Physical data

Width

12.5 mm / 0.492 inch

Height

110 mm / 4.331 inch

Depth from upper-edge of DIN-rail

107 mm / 4.213 inch

Mechanical data

Mounting type

DIN-35 rail

Material data

Fire load

1.374

Weight

86

Environmental requirements

Ambient temperature (operation)

-40 … +70 °C

Surrounding air temperature (storage)

-40 … +85 °C

Temperature range of connection cable per EN 61010-2-201

≥ (Tambient + 30 K)

Relative humidity

5 … 95 %

Operating altitude (max.)

2000

Standards and specifications

Conformity marking

CE

EMC immunity to interference

EN 61000-6-2; EN 61326-2-3; EN 50121-3-2

EMC emission of interference

EN 61000-6-4; EN 61326-2-3; EN 50121-3-2

Standards/specifications

EN 50121-3-2

EN 61010-1

EN 61373

Instruction Leaflet
  • RTD-Grenzwertschalter

    Download
Additional Information
  • Disposal; Electrical and electronic equipment, Packaging

    Download
Software for Interface-Products
  • WAGO Interface Configuration Software G2 SMALL

    Download
  • WAGO Interface Configuration Software G2 FULL

    Download
Compliance Search
  • Environmental Product Compliance 2857-533/000-001

    Download