Technical data
Configuration
Configuration options | DIP switch WAGO Interface Configuration Software WAGO Interface Configuration App WAGO Configuration Display DIP switch WAGO Interface Configuration Software WAGO Interface Configuration App WAGO Configuration Display |
Input
Input signal type | Potentiometer Resistance RTD sensors Potentiometers Resistor |
Input – RTD sensors
Sensor types (RTD) | Pt100 Pt200 Pt500 Pt1000 Pt5000 Pt10000 Pt10 … Pt20000 |
Sensor connection | 2-wire; 3-wire; 4-wire; differential |
Sensor power supply (RTD) max. | ≤ 0.5 mA |
Temperature measurement range (RTD) | -200 … 850°C |
Input – resistors
Input range (resistor) | 0 … 100 kΩ |
Input range (potentiometer) | 0 … 100 kΩ |
Output – digital
Switching voltage (DO) max. | Supply voltage (applied): −0.3 V |
Continuous current (DO) max. | 100 mA (no internal restriction) |
Number of switching thresholds (DO) | 1 or 2 (adjustable) |
Configurable rise/fall delay time (DO) | 0 … 60 s (via software) |
Output – relay
Dielectric strength (open contact) (AC, 1 min) | 1 |
Number of make/switch-on contacts | 1 |
Contact material (relay) | AgNi + Au |
Switching voltage (max.) | AC 250 V |
Limiting continuous current (relay; module assembly) | 6 A (≤ 60 °C); 3 A (60 … 70 °C) |
Dielectric strength (open contact) (AC, 1 min) | 1 kVrms |
Pull-in time (typ.) | 8 |
Drop-out time (typ.) | 4 |
Bounce time (typ.) | 8 |
Number of switching thresholds (relay) | 1 or 2 (adjustable) |
Configurable rise/fall delay time (relay) | 0 … 60 s (via software) |
Signal processing
Software filter (adjustable) | Moving average value (filter level: 30) |
Hysteresis | adjustable via DIP switch or software |
Step response (typ.) | 60 ms (2-wire); 360 ms (3-wire); 540 ms (4-wire); 360 ms (potentiometer) |
Measurement error
Transmission error (max.) | ± 1 K |
Temperature coefficient | ≤ 0.01 %/K |
Supply
Power supply type | 24 VDC |
Nominal supply voltage US | DC 24 V |
Supply voltage range | ±30 % |
Current consumption at nominal supply voltage | ≤ 40 mA (+ IDO) |
Notes
Note |
|
Safety and protection
Rated voltage of the measurement circuit connections per EN 61010-2-030 | AC 300 V |
Measurement category per EN/UL 61010-2-030 | CAT II (input) |
Note on insulation parameters | The digital output (DO) is at the potential of the supply. Temperature sensors are not intended for use in dangerous circuits, provided the external temperature sensors used do not have basic insulation in accordance with EN/UL 61010-1 (300 VAC; overvoltage category II; pollution degree 2). The digital output (DO) is at the potential of the supply |
Protection type | IP20 |
Connection data
Connection technology | Push-in CAGE CLAMP® |
WAGO connector | picoMAX® 5.0 |
Solid conductor | 0.2 … 2.5 mm² / 24 … 12 AWG |
Fine-stranded conductor | 0.2 … 2.5 mm² / 24 … 12 AWG |
Strip length | 9 … 10 mm / 0.35 … 0.39 inch |
Physical data
Width | 12.5 mm / 0.492 inch |
Height | 110 mm / 4.331 inch |
Depth from upper-edge of DIN-rail | 107 mm / 4.213 inch |
Mechanical data
Mounting type | DIN-35 rail |
Material data
Fire load | 1.391 |
Weight | 86.5 |
Environmental requirements
Ambient temperature (operation) | -40 … +70 °C |
Surrounding air temperature (storage) | -40 … +85 °C |
Temperature range of connection cable per EN 61010-2-201 | ≥ (Tambient + 10 K) |
Temperature range of connection cable per UL 61010-2-201 (min.) | 90 |
Standards and specifications
Conformity marking | CE |
EMC immunity to interference | EN 61000-6-2; EN 61326-2-3; EN 50121-3-2 |
EMC emission of interference | EN 61000-6-4; EN 61326-2-3; EN 50121-3-2 |
Standards/specifications | EN 50121-3-2 EN 61010-1 EN 61373 |