2857-535/000-001 - Temperature signal conditioner; Configuration via software; Supply voltage: 24 VDC
- Brand: Wago
- Product Code: 2857-535/000-001
- Available Quantity: 0
$654.50
Technical data
Configuration
Configuration options | WAGO Interface Configuration Software WAGO Configuration Display WAGO Interface Configuration App Rotary encoder switch |
Input
Input signal type | RTD sensors Potentiometer Resistance TC sensors |
Input – RTD sensors
Sensor types (RTD) | Pt10 … Pt2000 (expandable) |
Sensor connection | 2-wire; 3-wire; 4-wire; differential; potentiometer |
Sensor power supply (RTD) max. | ≤ 0.5 mA |
Temperature measurement range (RTD) | -200 … 850°C |
Measurement span (RTD) min. | 50 |
Input – TC sensors
Sensor types (TC) | Type J Type K Type E Type R Type N Type S Type T Type B Type C |
Temperature measurement range (TC) | -210 … 1200 °C (Type J); -200 … 1372 °C (Type K); -200 … 1000 °C (Type E); 250 … 1768 °C (Type R); -200 … 1300 °C (Type N); -50 … 1664 °C (Type S); -200 … 400 °C (Type T); 250 … 1820 °C (Type B); 0 … 2320 °C (Type C) |
Measurement span (TC) min. | 100 |
Cold junction compensation | ON/OFF (default: ON) |
Cold junction error | 3 K (typ. 2 K ) |
Input – resistors
Input range (resistor) | 0 … 10 kΩ |
Input range (potentiometer) | 0 … 10 kΩ |
Measurement span (min.) | 50 |
Output – MODBUS
Number of devices (max.) | 64 |
Addressing | via rotary encoder switch: 1 … 99 |
Parity | Even; others can be configured |
Connector | 6 x picoMAX® for daisy chain configuration |
Bus length (max.) | 1000 |
Terminating resistor | Can be activated; 150 Ω; 120 Ω + 1 nF |
Parameter | Read input registers (0x04):
|
Output – relay
Dielectric strength (open contact) (AC, 1 min) | 1 |
Number of changeover contacts | 1 |
Switching voltage (max.) | AC 250 V |
Limiting continuous current (relay; module assembly) | 6 A (≤ 60 °C); 3 A (60 … 70 °C) |
Dielectric strength (open contact) (AC, 1 min) | 1 kVrms |
Number of switching thresholds (relay) | 1 or 2 (adjustable) |
Configurable rise/fall delay time (relay) | 0 … 60 s (via software) |
Communication
Communication | Modbus® RTU |
Interface | RS-485 (2-wire) |
Number of devices (max.) | 64 |
Bus length (max.) | ≤ 1000 m |
Baud rate | 9.6 kBd … 19.2 kBd |
Terminating resistor | Can be activated; 150 Ω; 120 Ω + 1 nF |
Addressing | via rotary encoder switch: 1 … 99 |
Signal processing
Software filter (adjustable) | Moving average value (filter level: 30) |
Step response (typ.) | 130 ms (2-wire); 700 ms (3-wire); 700 ms (4-wire); 600 ms (Differential); 500 ms (Potentiometer); 150 ms (Cold junction compensation (OFF)); 400 ms (Cold junction compensation (ON)) |
Measurement error
Transmission error (typ.) | ≤ 0.1 % at full measurement span |
Transmission error for the set measurement range | ≤ (100 K/set measurement range [K]) % |
Temperature coefficient | ≤ 0.01 %/K |
Supply
Power supply type | 24 VDC |
Nominal supply voltage US | DC 24 V |
Supply voltage range | -60 … +30 % |
Current consumption at nominal supply voltage | ≤ 50 mA |
Notes
Note | This product is supplied with 24 VDC, which can be commoned using lateral push-in type jumper bars: (6.1) US+ (BR) and (6.2) GND 2 (BR). With this variant, it is necessary to ensure that the maximum permissible total current of 1 A is not exceeded. |
Safety and protection
Rated voltage of the measurement circuit connections per EN 61010-2-030 | AC 300 V |
Measurement category per EN/UL 61010-2-030 | CAT II (input) |
Note on insulation parameters | The service interface is located on the service interface potential. The DIN-rail contact (functional ground) is capacitively coupled to the communication interface. |
Protection type | IP20 |
Connection data
Connection technology | Push-in CAGE CLAMP® |
WAGO connector | picoMAX® 5.0 |
Solid conductor | 0.2 … 2.5 mm² / 24 … 12 AWG |
Fine-stranded conductor | 0.2 … 2.5 mm² / 24 … 12 AWG |
Strip length | 9 … 10 mm / 0.35 … 0.39 inches |
Connector | 6 x picoMAX® for daisy chain configuration |
Physical data
Width | 22.5 mm / 0.886 inches |
Height | 110 mm / 4.331 inches |
Depth from upper-edge of DIN-rail | 107 mm / 4.213 inches |
Mechanical data
Mounting type | DIN-35 rail |
Material data
Fire load | 1.796 |
Weight | 13 |
Environmental requirements
Pollution degree | 2 |
Ambient temperature (operation) | -40 … +70 °C |
Surrounding air temperature (storage) | -40 … +85 °C |
Temperature range of connection cable per EN 61010-2-201 | ≥ (Tambient + 10 K) |
Temperature range of connection cable per UL 61010-2-201 (min.) | 90 |
Relative humidity | 5 … 95 % (non-condensing) |
Operating altitude (max.) | 2000 |
Standards and specifications
Conformity marking | CE |
EMC immunity to interference | EN 61000-6-2; EN 61326-2-3 |
EMC emission of interference | EN 61000-6-3; EN 61326-2-3 |
Standards/specifications | EN 61010-1 EN 61373 |