857-812 - JUMPFLEX® signal conditioner; temperature; thermocouples of type K S, B, and R; configurable

  • Brand: Wago
  • Product Code: 857-812
Description: Short description: WAGOs temperature signal conditioner records signals from thermocouples (type K, S, B, R) and converts the temperature signal into a standard analog signal at the output. Features: For thermocouples of type K, S, B and R Cold junction compensation (On/Off) Calibrated measurement range switching Detects a sensor wire break Detects measurement range underflow/overflow Clipping capability for analog signal limitation to output end values Safe 3-way isolation with 2.5 kV test voltage per EN 61140
Description: Short description: WAGOs temperature signal conditioner records signals from thermocouples (type K, S, B, R) and converts the temperature signal into a standard analog signal at the output. Features: For thermocouples of type K, S, B and R Cold junction compensation (On/Off) Calibrated measurement range switching Detects a sensor wire break Detects measurement range underflow/overflow Clipping capability for analog signal limitation to output end values Safe 3-way isolation with 2.5 kV test voltage per EN 61140
  • Available Quantity: 0

$330.50

Technical data
Configuration

Configuration options

DIP switch

DIP switch

Input

Input signal type

TC sensors

Input – TC sensors

Sensor types (TC)

Type K

Type S

Type B

Type R

Temperature measurement range (TC)

0 … 1200 °C (Type K); 0 … 1600 °C (Type S); 600 … 1800 °C (Type B); 0 … 1600 °C (Type R)

Cold junction compensation

On/Off (Default: On)

Cold junction error

3 K (typ. 2 K )

Output – analog

Output signal type

Current

Voltage

Output signal (V)

0 … 5 V

1 … 5 V

0 … 10 V

2 … 10 V

Output signal (A)

0 … 10 mA

2 … 10 mA

0 … 20 mA

4 … 20 mA

Load impedance (voltage output)

≥ 2 kΩ

Load impedance (current output)

≤ 600 Ω

Signal processing

Step response (typ.)

60 ms (Cold junction compensation (OFF)); 120 ms (Cold junction compensation (ON))

Measurement error

Transmission error (typ.)

≤ 0.1 % at full measurement span

Transmission error for the set measurement range

≤ (150 K/set measurement range [K]) %

Temperature coefficient

≤ 0.04 %/K

Supply

Power supply type

24 VDC

Nominal supply voltage US

DC 24 V

Supply voltage range

±30 %

Current consumption at nominal supply voltage

≤ 40 mA

Safety and protection

Protection type

IP20

Connection data

Connection technology

Push-in CAGE CLAMP®

Solid conductor

0.08 … 2.5 mm² / 28 … 14 AWG

Fine-stranded conductor

0.34 … 2.5 mm² / 22 … 14 AWG

Strip length

9 … 10 mm / 0.35 … 0.39 inch

Physical data

Width

6 mm / 0.236 inch

Height

94 mm / 3.701 inch

Depth from upper-edge of DIN-rail

97.8 mm / 3.85 inch

Mechanical data

Mounting type

DIN-35 rail

Material data

Weight

35.7

Environmental requirements

Ambient temperature (operation)

-25 … +70 °C

Surrounding air temperature (storage)

-40 … +85 °C

Relative humidity

5 … 95 % (no condensation permissible)

Operating altitude (max.)

2000

Standards and specifications

Conformity marking

CE

EMC immunity to interference

EN 61000-6-2

EMC emission of interference

EN 61000-6-4

Bid Text
  • 857-812

    Download
  • 857-812

    Download
Instruction Leaflet
  • Messumformer und Trennverstärker

    Download
Additional Information
  • Disposal; Electrical and electronic equipment, Packaging

    Download
CAD data
  • 2D/3D Models 857-812

    Download
CAE data
  • EPLAN Data Portal 857-812

    Download
  • WSCAD Universe 857-812

    Download
  • ZUKEN Portal 857-812

    Download
Compliance Search
  • Environmental Product Compliance 857-812

    Download