- Expansion module for the product series PSC1-C-10
- Extension with up to 18 digital in-/outputs
- 2 additional signalling outputs
- 2 Relay contacts
- Connection for all conventional safety switchgear up to PL e to ISO 13849-1
Data
Ordering data
Product type description | PSC1-E-33-12DI-6DIO-4RO |
Article number (order number) | 103008456 |
EAN (European Article Number) | 4030661455174 |
eCl@ss number, version 9.0 | 27-24-22-04 |
eCl@ss number, version 11.0 | 27-24-22-04 |
eCl@ss number, version 12.0 | 27-24-22-04 |
ETIM number, version 7.0 | EC001419 |
ETIM number, version 6.0 | EC001419 |
Approvals - Standards
Certificates | TÜV cULus EAC |
General data
Terminal (mechanical) | Removable screw terminals |
Gross weight | 300 g |
General data - Features
Number of relay outputs (1-channel) | 4 |
Number of digital fail-safe inputs | 6 |
Number of digital fail-safe in-/outputs | 6 |
Number of signalling outputs | 2 |
Mechanical data
Mounting | can be clipped into standard rail |
Mechanical data - Connection technique
Cable section, minimum | 0.2 mm² |
Cable section, maximum | 2.5 mm² |
Wire cross-section, minimum | 24 AWG |
Wire cross-section, maximum | 12 AWG |
Mechanical data - Dimensions
Width | 67.5 mm |
Height | 100 mm |
Depth | 115 mm |
Ambient conditions
Degree of protection | IP20 |
Ambient temperature, minimum | +0 °C |
Ambient temperature, maximum | +50 °C |
Storage and transport temperature, minimum | -25 °C |
Storage and transport temperature, maximum | +70 °C |
Relative humidity, minimum | 5 % |
Relative humidity, maximum | 85 % |
Note (Relative humidity) | non-condensing |
Permissible installation altitude above sea level, maximum | 2,000 m |
Ambient conditions - Insulation values
Overvoltage category | III |
Degree of pollution to IEC/EN 60664-1 | 2 |
Electrical data
Operating voltage, minimum | 20.4 VDC |
Operating voltage, maximum | 28.8 VDC |
Electrical data - Safety digital outputs
Rated operating current (safety outputs) | 2,000 mA |
Electrical data - Safe relay outputs
Voltage, Utilisation category AC-15 | 230 VAC |
Current, Utilisation category AC-15 | 2 A |
Voltage, Utilisation category DC-13 | 24 VDC |
Current, Utilisation category DC-13 | 2 A |
Electrical data - Electromagnetic compatibility (EMC)
Electromagnetic compatibility | DIN EN 62061 DIN EN 61800-3 |
Interfering radiation | DIN EN 61000-6-4 |
EMC rating | DIN EN 61000-6-7 DIN EN 61326-3 DIN EN 61000-6-2 |