101189095 - PROTECT-IE-11-SK
- Brand: Schmersal
- Product Code: 101189095
- Input for up to 4 sensors per interface e.g.: magnetic safety switches type BNS, emergency stop devices, interlocking devices and others
- 2 safety contacts
Data
Ordering data
Product type description | PROTECT-IE-11-SK |
Article number (order number) | 101189095 |
EAN (European Article Number) | 4250116202232 |
eCl@ss number, version 9.0 | 27-37-18-19 |
eCl@ss number, version 11.0 | 27-37-18-19 |
eCl@ss number, version 12.0 | 27-37-18-19 |
ETIM number, version 7.0 | EC001449 |
ETIM number, version 6.0 | EC001449 |
Available until | 31.12.2022 |
Approvals - Standards
Certificates | cULus EAC |
General data
Standards | EN 60947-5-1 EN ISO 13849-1 IEC 61508 IEC/EN 60204-1 |
Climatic stress | EN 60068-2-78 |
Enclosure material | Glass-fibre reinforced thermoplastic, ventilated |
Gross weight | 140 g |
General data - Features
Stop-Category | 0 |
Electronic Fuse | Yes |
Wire breakage detection | Yes |
Cross-circuit detection | Yes |
Removable Terminals | Yes |
Automatic reset function | Yes |
Earth connection detection | Yes |
Integral system diagnostics, general | Yes |
Number of auxiliary contacts | 1 |
Number of LEDs | 5 |
Number of openers | 1 |
Number of shutters | 1 |
Number of safety contacts | 2 |
Mechanical data
Mechanical life, minimum | 10,000,000 Operations |
Mounting | Snaps onto standard DIN rail to EN 60715 |
Mechanical data - Connection technique
Type of connection | Screw connection, plug-in |
Terminal designations | IEC/EN 60947-1 |
Cable section, minimum | 0.14 mm² |
Cable section, maximum | 1.5 mm² |
Mechanical data - Dimensions
Width | 48 mm |
Height | 126 mm |
Depth | 61 mm |
Ambient conditions
Degree of protection of the enclosure | IP20 |
Degree of protection of the mounting space | IP20 |
Degree of protection of clips or terminals | IP20 |
Ambient temperature, minimum | -25 °C |
Ambient temperature, maximum | +55 °C |
Storage and transport temperature, minimum | -40 °C |
Storage and transport temperature, maximum | +85 °C |
Resistance to vibration to EN 60068-2-6 | 10...55 Hz, Amplitude 0.35 mm, ± 15 % |
Restistance to shock | 30 g / 11 ms |
Ambient conditions - Insulation values
Rated impulse withstand voltage U | 0.8 kV |
Overvoltage category | III |
Degree of pollution to VDE 0110 | 2 |
Electrical data
Rated operating voltage | 24 VDC -15% / +20%, residual ripple max. 10 % |
Rated AC voltage for controls at DC minimum | 20.4 VDC |
Rated control voltage at DC, maximum | 28.8 VDC |
Electrical power consumption | 1.7 W |
Input resistance at Ue | 2,900 Ω |
Contact resistance, maximum | 0.1 Ω |
Note (Contact resistance) | in new state |
Drop-out delay in case of "emergency stop", maximum | 20 ms |
Pull-in delay at automatic start, maximum | 20 ms |
Electrical data - Safe relay outputs
Voltage, Utilisation category DC-13 | 24 VDC |
Current, Utilisation category DC-13 | 2 A |
Switching capacity, minimum | 10 VDC |
Switching capacity, minimum | 10 mA |
Switching capacity, maximum | 24 VAC |
Switching capacity, maximum | 2 A |
Electrical data - Digital inputs
Input signal, HIGH Signal "1" | 19 - 28,8 VDC |
Input signal, LOW Signal "0" | 0 - 1 VDC |
Conduction resistance, maximum | 40 Ω |
Electrical data - Digital Output
Voltage, Utilisation category DC-12 | 24 VDC |
Current, Utilisation category DC-12 | 0.1 A |
Electrical data - Relay outputs (auxiliary contacts)
Switching capacity, maximum | 24 VDC |
Switching capacity, maximum | 0.1 A |
Electrical data - Electromagnetic compatibility (EMC)
EMC rating | EMC-Directive |