859-732 - Optocoupler module; Nominal input voltage: 24 VDC; Output voltage range: 3 … 30 VDC; Limiting continuous current: 0.5 A; 1 changeover contact; Red status indicator; Module width: 6 mm; gray
- Brand: Wago
- Product Code: 859-732
- Available Quantity: 0
$61.25
Technical data
Control circuit
Nominal input voltage UN | DC 24 V |
Input voltage range (low level) | DC 0 … 5 V |
Input voltage range (high level) | DC 15 … 42 V |
Nominal input current at UN | 5.3 mA |
Load circuit
Circuit type | 3-wire connection Changeover contact output |
Limiting continuous current | 0.5 A |
Peak output current | 4 |
Nominal output voltage | DC 24 V |
Output voltage range | DC 3 … 30 V |
Voltage drop at output (max.) | ≤ DC 1.5 V |
Leakage current at rated voltage | ≤ 1.5 mA |
Switching current (min.) | 0.5 mA |
Turn-on time | ≤ 25 µs |
Turn-off time | ≤ 150 µs |
Switching frequency | ≤ 1.5 kHz |
Signaling
Status indicator | Red LED |
Safety and protection
Rated voltage | 300 |
Overvoltage category | II |
Pollution degree | 2 |
Dielectric strength (control/load circuit) (AC, 1 min) | 3.51 kVrms |
Insulation type (control/load circuit) | Basic insulation |
Insulation type (adjacent devices) | Reinforced insulation (safe isolation) |
Protection type | IP20 |
Note on protection type | in connected state or when using 859-525 end plate |
Notes
Note | Optocouplers and solid state relays are designed for use in signal processing networks, which are not supplied by the low-voltage power supply networks. |
Connection data
Connection technology | CAGE CLAMP® |
Solid conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Fine-stranded conductor | 0.08 … 2.5 mm² / 28 … 14 AWG |
Fine-stranded conductor; with insulated ferrule | 0.08 … 1.5 mm² / 28 … 16 AWG |
Strip length | 5 … 6 mm / 0.2 … 0.24 inch |
Physical data
Width | 6 mm / 0.236 inch |
Height | 91 mm / 3.583 inch |
Depth from upper-edge of DIN-rail | 56 mm / 2.205 inch |
Mechanical data
Mounting type | DIN-35 rail |
Mounting position | Horizontal (standing/lying); vertical |
Material data
Color | gray |
Fire load | 0.313 |
Weight | 19.6 |
Environmental requirements
Ambient temperature (operation at UN) | -25 … 55 °C |
Surrounding air temperature (storage) | -25 … +70 °C |
Processing temperature | -25 … +50 °C |
Temperature range of connection cable per EN 61010-2-201 | ≥ (Tsurrounding air + 20 K) |
Relative humidity | 5 … 85 % (no condensation permissible) |
Operating altitude (max.) | 2000 |
Standards and specifications
Standards/specifications | EN 61010-2-201 EN 61000-6-2 EN 61000-6-3 UL 508 |